1 .1 .14 TC 4 in a multiple burner system with 3 valves
installed in series
Tightness control TC 4 checks the central shut-off valve V1
and the gas solenoid valve V2 for tightness.
Valve V2 can only be checked for tightness when the
pressure downstream of V2 approximately corresponds to
the atmospheric pressure. The gas solenoid valve VAS and
the pressure switch DG
VAS
are used to relieve the pressure.
The pressure switch must be adjusted in such a way so that
enough pres- sure is relieved and no air can get into the
pipework.
Once the start-
is checked. If the pressure downstream of V2 is correct,
the VAS closes and the tightness test is started.
Once the tightness test has been carried out successfully,
the tightness control TC 4 opens the main valves V1 and
V2 with the OK enable signal and enables the
downstream burner control units.
V1 and V2: quick or slow opening valves with start rate.
p
u
= Inlet pressure
V
P
= Test volume
TC 4
DG
PZ
p
u
2
V1
V2
p
u
p
Z
V
P
TC 4
1 2 3 4 5 6 7 8 9 10 11 12 13
PZ
k1
DG
VAS
OK
k1
V2
VAS
K1
V1
L1(+)
N(-)
PZ
D
G
V
A
S
V
A
S