![krom schroeder BCU 570 Operating Instructions Manual Download Page 22](http://html.mh-extra.com/html/krom-schroeder/bcu-570/bcu-570_operating-instructions-manual_2004652022.webp)
GB-22
D
GB
F
NL
I
E
Technical data
Electrical data
Mains voltage:
BCU 570Q: 120 V AC, -15/+10%, 50/60 Hz, ±5%,
BCU 570W: 230 V AC, -15/+10%, 50/60 Hz,
±5%,
for grounded or ungrounded mains.
Flame control:
with UV sensor or ionization sensor.
For intermittent or continuous operation.
Flame signal current:
ionization control: 1 – 25 μA,
UV control: 1 – 35 μA.
Ionization cable, UV cable:
max. 100 m (164 ft).
Contact rating:
valve outputs V1, V2, V3 and V4 (terminals 13, 14,
15, 57) as well as actuator (terminals 53, 54
and 55):
max. 1 A each, cos φ ≥ 0.6,
total current for the simultaneous activation of the
valve outputs (terminals 13, 14, 15, 57) and of the
actuator (terminals 53, 54, 55):
max. 2.5 A,
fan (terminal 58):
max. 3 A (start-up current: 6 A < 1 s),
signalling contact for operating and fault signals:
max. 1 A (external fuse required).
Number of operating cycles:
The fail-safe outputs (valve outputs V1, V2, V3
and V4) are monitored for correct functioning and
are thus not subject to a max. number of operating
cycles.
Control actuator (terminals 53, 54 and 55):
max. 250,000,
signalling contact for operating signals:
max. 250,000,
signalling contact for fault signals:
max. 10,000,
On/Off button:
max. 10,000,
Reset/Information button:
max. 10,000.
Input voltage of signal inputs:
Rated value
120 V AC
230 V AC
Signal “1”
80 – 132 V
160 – 253 V
Signal “0”
0 – 20 V
0 – 40 V
Signal input current:
Signal “1”
max. 5 mA
Fuses, replaceable, F1: T 3.15A H,
F2: T 5A H, pursuant to IEC 60127-2/5.
Mechanical data
Weight: 0.7 kg.
Dimensions (W × H × D): 102 × 115 × 112 mm.
Connections:
Screw terminals:
nominal cross-section 2.5 mm²,
wire cross-section (rigid) min. 0.2 mm²,
wire cross-section (rigid) max. 2.5 mm²,
wire cross-section AWG/kcmil min. 24,
wire cross-section AWG/kcmil max. 12.
Spring force terminals:
nominal cross-section 2 x 1.5 mm²,
wire cross-section min. 0.2 mm²,
wire cross-section AWG min. 24,
wire cross-section AWG max. 16,
wire cross-section max. 1.5 mm²,
rated current 10 A (8 A UL),
to be observed in case of daisy chain.
Environment
Storage temperature: -20 to +60°C (-4 to +140°F).
Ambient temperature:
-20 to +60°C (-4 to +140°F),
no condensation permitted.
Enclosure: IP 20 pursuant to IEC 529.
Installation location: min. IP 54 (for installation in a
control cabinet).
Designed lifetime
This information on the designed lifetime is based on
using the product in accordance with these operating
instructions. Once the designed lifetime has been
reached, safety-relevant products must be replaced.
Designed lifetime (based on date of manufacture):
20 years.
You can find further explanations in the applicable
rules and regulations and on the afecor website
(www.afecor.org).
This procedure applies to heating systems. For
thermoprocessing equipment, observe local regu-
lations.
Logistics
Transport
Protect the unit from external forces (blows, shocks,
vibration). On receipt of the product, check that the
delivery is complete, see page 2 (Part designa-
tions). Report any transport damage immediately.
Storage
Store the product in a dry and clean place.
Storage temperature: see page 22 (Technical data).
Storage time: 6 months before using for the first
time. If stored for longer than this, the overall service
life will be reduced by the corresponding amount of
extra storage time.
Packaging
The packaging material is to be disposed of in ac-
cordance with local regulations.
Disposal
Components are to be disposed of separately in
accordance with local regulations.