GB-14
D
GB
F
NL
I
E
Pilot burner = UVC/main burner = UVC:
▷
Parameter 04 = 6
9
7
8
6
5
UVC 1
4
3
2
1
N
PE
L
UVC 1
4
3
2
1
Pilot burner = UVC/main burner = ionization:
▷
Parameter 04 = 7
I
9
7
8
6
5
N
PE
L
UVC 1
4
3
2
1
Pilot burner = UVC/main burner = UVS:
▷
Parameter 02 ≥ 5 µA
▷
Parameter 04 = 8
9
7
8
6
5
N
PE
L
UVC 1
4
3
2
1
UVS
1
2
3
Adjustment
In certain cases, it may be necessary to change the
parameters set at the factory. Using the separate
software package BCSoft and a PC opto-adapter, it
is possible to modify parameters on the BCU, such
as the pre-purge time or the behaviour in the event
of a flame failure.
▷
The software package and the opto-adapter
are available as accessories – see page 27
(Accessories).
▷
Changed parameters are saved on the integrated
parameter chip card.
▷
The factory settings are secured with a program-
mable password.
▷
If the password has been changed, the end cus-
tomer can look up the changed password in the
plant documentation or ask the system supplier.
Commissioning
▷
During operation, the 7-segment display shows
the program status:
00
Standby
H0
Delay
A
Approaching minimum capacity
A0
Cooling
01
Fan run-up time
A1
Pre-ventilation
A
Approaching maximum capacity
H1
Delay
P0
Pre-purge
P1
Pre-purge
A
Approaching ignition capacity
Valve check
02
Safety time 1 t
SA1
A2
Safety time 1 t
SA1
03
Flame proving period 1
A3
Flame proving period 1
04
Burner 1 operation
A4
Burner 1 operation
05
Burner 2 waiting time
A5
Delay
H5
Delay time during burner 2 waiting time
06
Safety time 2 t
SA2
A6
Safety time 2 t
SA2
07
Flame proving period 2 t
FS2
A7
Flame proving period 2 t
FS2
08
Burner 2 operation
A8
Burner 2 operation
H8
Delay
––
Device Off
U I
Remote control (with OCU)
Data transfer (programming mode)
0
.
0
.
(blinking dots) Manual mode
WARNING
Risk of explosion! Check the system for tightness
before commissioning.
Do not start the BCU until the parameter settings
and wiring are correct and the faultless processing
of all input and output signals has been ensured.
1
Switch on the system.
▷
The display indicates
––
.
Switch on the BCU by pressing the On/Off but-
ton.
▷
The display indicates
00
.
▷
If the display blinks (fault), reset the BCU by
pressing the Reset/Information button.