Checking the usage
JSAV
Safety shut-off valve for securing downstream fittings
against excess gas pressure.
This function is only guaranteed when used within
the specified limits – see page 7 (Technical data).
Any other use is considered as non-compliant.
Type code
Code
Description
JSAV
Safety shut-off valve
5 – 40
Nominal size
R
N
F
Rp internal thread to ISO 7-1
NPT internal thread
Flange PN 16 to ISO 7005
40
Max. inlet pressure p
u
= 4 bar (58 psig)
/
/
Upper trip pressure p
do
Upper and lower trip pressure p
do
/p
du
-0
-
Without pressure test point
Screw plug at the inlet and outlet
Part designations
JSAV 5
4
1
2
6
7
5
3
JSAV 40
1
2
9
7
6
5
8
3
4
Measuring unit
Breather screw plug
Reset cap
4
Impulse line connection
5
Inlet
6
Outlet
7
Arrow of direction of flow
8
Inlet p
u
measuring connection
9
Outlet p
d
measuring connection
Type label
▷
Max. inlet pressure p
u
, upper trip pressure p
do
and lower trip pressure p
du
, ambient tempera-
ture T: see type label.
www.kromschroeder.com
D-49018 Osnabrück, Germany
JSAV
p
u
: 4 bar
p
du
: 10 mbar
(8..16)
p
do
: 140 mbar (10..210)
T: -20 °C..+60 °C
Klasse A IS
CE-0085AS0202
www.kromschroeder.com
D-49018 Osnabrück, Germany
Installation
CAUTION
Please observe the following to ensure that the
JSAV is not damaged during installation:
– Sealing material, cuttings and other impurities
must not be allowed to get into the housing.
– We recommend installing a filter upstream of the
JSAV in order to protect it against impurities in
the pipe.
– The installation location must be dry. Do not
store or install the JSAV in the open air.
– Install the JSAV in the pipe free of mechanical
stress.
– Do not clamp the unit in a vice or use it as a
lever. On the JSAV..R, only secure the valve by
holding the octagon at the inlet or outlet with a
suitable spanner. Risk of external leakage.
– Max. inlet pressure p
u
4 bar (58 psig).
▷
Installation in the vertical or horizontal position,
never upside down.
The housing must not be in contact with ma-
sonry. Minimum clearance 20 mm (0,78"). Ensure
that there is sufficient space for installation and
adjustment.
JSAV..R: seal pipe with approved sealing material.
Remove screw caps from the inlet and outlet on
the JSAV.
▷
Note direction of flow.