background image

GB-6

D

GB

F

NL

I

E

 6 

  Follow the reverse procedure when reassembling.

 7 

 Connect the impulse line to the JSAV.

 8 

 Check tightness and function, see page  3 

(Tightness test) and page  4 (Checking the 
function).

JSAV 40

 

The measuring unit is supplied with the valve disc 

assembled. 1 O-ring and 4 screws are enclosed.

  

 Detach the impulse line from the JSAV.

4

5

6

3

8

9

7

 

Ensure that the O-ring is fitted in the new measur-
ing unit, see Figure

  9 

.

 0 

 Replace the O-ring on the housing. The O-ring 

is part of the seal set.

 

The seal set is available separately as a spare part.

  

  Follow the reverse procedure when reassembling.

  

 Connect the impulse line to the JSAV.

  

 Check tightness and function, see page  3 

(Tightness test) and page  4 (Checking the 
function).

Replacing the valve disc

 

The valve disc has to be replaced if the JSAV 

is leaking.

 

We recommend cleaning the O-ring seats and 

lightly greasing the O-rings with Klüber Nontrop 

ZB91 DIN before installation.

  

 Depressurize the system.

JSAV 5

 

The valve disc is supplied with a complete seal 

set. We recommend replacing all seals.

  

 Detach the impulse line from the JSAV.

5

17

15

9

4

18

3

19

6

7

10

8

11

10

12

16

13

14

    First insert 

the washer 

into the valve 

disc, and then 

the O-ring.

 

Ensure that the O-ring is fitted in the new measur-
ing unit, see Figure

  6 

.

 7 

  Follow the reverse procedure when reassembling.

 8 

 Connect the impulse line to the JSAV.

 9 

 Check tightness and function, see page  

(Tightness test) and page  4 (Checking the 
function).

JSAV 40

 

The valve disc is supplied with a complete seal 

set. We recommend replacing all seals.

  

 Detach the impulse line from the JSAV.

Summary of Contents for JSAV 25

Page 1: ...only be carried out by qualified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM sp...

Page 2: ...com D 49018 Osnabr ck Germany JSAV pu 4 bar pdu 10 mbar 8 16 pdo 140 mbar 10 210 T 20 C 60 C Klasse A IS CE 0085AS0202 www kromschroeder com D 49018 Osnabr ck Germany Installation CAUTION Please obser...

Page 3: ...on nut and compression fitting onto the impulse line On the JSAV T remove the blind plug and con nect an NPT 1 8 impulse line 5 Install the impulse line and seal with approved sealing material Ensure...

Page 4: ...pdo according to the outlet pressure pd of the pressure regulator 20 0 40 60 80 100 140 180 220 260 300 340 50 100 150 200 250 300 350 400 450 500 pd mbar p do mbar VSBV JSAV 2 Remove the breather scr...

Page 5: ...pressures pdo and pdu on the adhesive label s 10 Screw in the breather screw plug 11 Check tightness and function see page 3 Tightness test and page 4 Checking the function Resetting Ensure that the...

Page 6: ...st and page 4 Checking the function Replacing the valve disc The valve disc has to be replaced if the JSAV is leaking We recommend cleaning the O ring seats and lightly greasing the O rings with Kl be...

Page 7: ...c and replace if necessary Selecting spare parts see free PartDetective DVD www kromschroeder com Products DVD PartDetective D GB Replacing spare parts see page 5 Replacing the measuring unit see page...

Page 8: ...d functions must be checked in accordance with the section entitled Maintenance If the product passes the aforementioned function tests you can continue to use it until the next sched uled maintenance...

Reviews: