  Press the Reset/Information button on the BCU 

to confirm the new parameter settings.

Commissioning

 

During operation, the 7-segment display shows 
the program status:

  00

  Standby

  H0

  Delay

  A 

  Approaching minimum capacity

  A0

  Cooling

  01

  Fan run-up time

  A1

  Pre-ventilation

  A 

  Approaching maximum capacity

  H1

  Delay

  P0

  Pre-purge

  P1

  Pre-purge

  A  

  Approaching ignition capacity

 

  Valve check

  02

  Safety time 1 t

SA1

 

  A2

  Safety time 1 t

SA1

  03

  Flame proving period 1 t

FS1

  A3

  Flame proving period 1 t

FS1

  04

  Burner 1 operation

  A4

  Burner 1 operation

  05

  Burner 2 waiting time

  A5

  Delay

  H5

  Delay time during burner 2 waiting time

  06

  Safety time 2 t

SA2

  A6

  Safety time 2 t

SA2

  07

  Flame proving period 2 t

FS2

  A7

  Flame proving period 2 t

FS2

  08

  Burner 2 operation

  A8

  Burner 2 operation

  H8

  Delay

  –– 

  Device Off
  Data transfer (programming mode)

 

0

.

0

.

  (blinking dots) Manual mode

   

XX

  Low NO

x

 operation in program step XX

    

XX

  High temperature operation in program 

step XX

 

Units with SafetyLink function (BCU with bus 
module BCM..S1) may only be commissioned 
using BCSoft. Further information can be found 
in Technical Information bulletin BCU 46x or 
BCU 480.

 WARNING

Risk of explosion! Check the system for tightness 
before commissioning.
Do not start the BCU until the parameter settings 
and wiring are correct and the faultless processing 
of all input and output signals complies with the 
local standards.

 1 

 Switch on the system.

 

The display shows 

 ––

.

  

 Switch on the BCU by pressing the On/Off but-

ton.

 

The display shows 

 00

.

 

The display blinks and indicates 

 E

XXX

. A reset-

table fault message is signalled. Reset the BCU 
by pressing the Reset/Information button.

 

The display blinks without indicating “

E

”. A warn-

ing message is signalled. Once the fault has been 
eliminated, the display stops blinking and the 
BCU continues the program run.

BCU 460..F0
 3 

 Apply the start-up signal to terminal 1.

 

The display shows 

01

.

 

The display shows 

02

. The gas valves open and 

the burner ignites. Safety time 1 starts to elapse.

 

The display indicates 

03

 during flame proving 

period 1.

 

The display shows 

04

. The burner is in opera-

tion.

BCU 46x..F1, BCU 46x..F3

 

If the air actuator is activated externally for cool-
ing in the start-up position, the display indicates 

 A0

.

 3 

 Apply the start-up signal to terminal 1.

 

The display indicates 

01

 or 

A1

 if the air actua-

tor has been activated.

 

The display indicates 

02

 or 

A2

 if the air actua-

tor has been opened. The gas valves open and 
the burner ignites. Safety time 1 starts to elapse.

 

The display indicates 

03

 during flame prov-

ing period 1 or 

A3

 if the air actuator has been 

opened.

 

The display indicates 

04

 or 

A4

 if the air actua-

tor has been opened. The burner is in operation.

BCU 480..F1/F3

 

If the air actuator is activated externally for cool-
ing in the start-up position, the display indicates 

 A0

.

 3 

 Apply the start-up signal to terminal 1.

 

The display indicates 

01

 or 

A1

 if the air actua-

tor has been opened.

 

The display indicates 

02

 or 

A2

 if the air actua-

tor has been opened. The gas valves open, the 
pilot burner (burner 1) ignites and safety time 1 
starts to elapse.

 

The display indicates 

03

 during flame prov-

ing period 1 or 

A3

 if the air actuator has been 

opened.

Summary of Contents for BCU 46 Series

Page 1: ...ons WARNING Indicates possible danger to life and limb CAUTION Indicates possible material damage All interventions may only be carried out by qualified gas technicians Electrical interventions may on...

Page 2: ...4 burner control unit 60 65 80 Series 460 Series 465 Series 480 Q W Mains voltage 120 V AC 50 60 Hz 230 V AC 50 60 Hz 1 2 3 8 Ignition transformer duty cycle 100 20 100 33 P0 P1 P2 P3 P6 P7 Flange pl...

Page 3: ...ion CAUTION Please observe the following to ensure that the BCU is not damaged The device must not be installed in a public place It must be accessible to authorized personnel only Unauthorized person...

Page 4: ...hip card CAUTION Please observe the following to ensure that the BCU is not damaged Different power supply for the gas valves The following combinations of BCU and LM are allowed BCU 4xx E1 LM E1 powe...

Page 5: ...s without authentica tion mechanisms Use shielded RJ45 plugs Cable length max 100 m between 2 subscrib ers Profinet Profibus installation guidelines see www profibus com Ethernet installation guidelin...

Page 6: ...s in accordance with the manufacturer s instructions The protective circuit prevents high voltage peaks which can cause malfunctioning of the BCU Install the ignition cable in the BCU in the desig nat...

Page 7: ...82 81 80 95 96 97 51 21 BM 23 22 85 86 87 92 91 90 54 24 N1 52 53 BM 55 25 N1 56 26 N1 F1 BCU E1 1 N1 N1 N1 N1 N1 N1 N1 N1 p U 2 230 V UVS I Z 3 1 2 4 6 5 7 40 41 35 39 LDS Start 1 F2 BCU E0 HT PE PE...

Page 8: ...1 21 BM 23 22 85 86 87 92 91 90 54 24 N1 52 53 BM 55 25 N1 56 26 N1 1 N1 N1 N1 N1 N1 N1 N1 N1 p U 2 230 V UVS I Z 3 1 2 4 6 5 7 40 41 35 39 P LDS Start 1 A HT PE PE PE PE PE 65 34 66 v Luft N1 67 BCU...

Page 9: ...23 22 85 86 87 92 91 90 54 24 N1 52 53 BM 55 25 N1 56 26 N1 1 N1 N1 N1 N1 N1 N1 N1 N1 p U 2 230 V UVS I Z 3 1 2 4 6 5 7 40 41 35 39 P LDS Start 1 A HT PE PE PE PE PE 65 34 66 v Luft N1 67 DW 2 DW 1 P...

Page 10: ...96 97 51 21 BM 23 22 85 86 87 92 91 90 54 24 N1 52 53 BM 55 25 N1 56 26 N1 1 N1 N1 N1 N1 N1 N1 N1 N1 N1 p U 2 230 V UVS 3 1 2 4 6 5 7 40 41 35 39 P LDS Start 1 Start 2 A PE PE PE PE PE 66 V Luft 67 P...

Page 11: ...7 40 41 35 39 E0 IC 40 PE 19 18 16 15 14 12 11 10 8 7 5 4 2 1 A AC D DC M mA L N 2221 20 R 66 67 64 65 40 41 56 26 N1 0 90 90 GB 11 D GB IC 40 connected to BCU LM F1 staged control Parameter I020 2 S...

Page 12: ...1 4 3 2 1 54 24 PE BM 22 Z 51 21 BM PE N1 1 N1 BCU 480 Pilot burner single electrode operation main burner ionization Pilot burner in single electrode operation Ionization control for main burner Par...

Page 13: ...behaviour in the event of a flame failure 1 Set the parameters using BCSoft For reasons of network security it is not possible to access the unit via the network using BCSoft The software package and...

Page 14: ...e display shows 00 The display blinks and indicates EXXX A reset table fault message is signalled Reset the BCU by pressing the Reset Information button The display blinks without indicating E A warn...

Page 15: ...ignal XX X is displayed instead of the program status 3 Press the Reset Information button for 1 s The display shows S 3 step 3 The BCU will start the second stage of the burner The display runs to 0...

Page 16: ...DANGER To avoid harm to persons and damage to the unit please observe the following Electric shocks can be fatal Before working on possible live components ensure the unit is disconnected from the po...

Page 17: ...the flame rod as the result of soot dirt or moisture on the insulator Flame rod not correctly positioned at the flame edge Terminal boot not properly connected to flame rod Gas air ratio incorrect Fl...

Page 18: ...heck the settings for capacity control during operation Press the Reset Information button on the BCU 2 1 E The display blinks and indicates E 21 Inputs 40 and 41 are activated simultaneously Check in...

Page 19: ...pressure Set DGpu 2 to the correct inlet pressure Check the wiring The test pressure between V1 and V2 has not decreased Check the installation The test period is too long Check parameter A056 Measur...

Page 20: ...9 6 E 9 8 E 9 4 E The display indicates E 89 E 94 E 95 E 96 E 97 E 98 or E 99 System fault the BCU has performed a safety shut down The cause may be a unit defect or abnormal EMC influence Ensure tha...

Page 21: ...d signal from actua tor Check the butterfly valve and the function of the limit switches in the actuator Check the wiring Check the actuator If the fault cannot be remedied by doing this remove the un...

Page 22: ...settings again Replace defective parameter chip card 1 E The display blinks and indicates E 1 No input signal for the valve proof of closure switch POC during standby Check the wiring Mains voltage m...

Page 23: ...at this will increase the signal running times to and from the individual units Poor shielding Check whether the shield is connected to the shield clips in the PROFIBUS DP plugs in full and over a wid...

Page 24: ...as risen to the specified setpoint again 0 E 1 E 6 E 2 E 4 E 3 E 5 E 7 E 8 E 9 E The display blinks and indicates E 0 E 1 E 2 E 3 E 4 E 5 E 6 E 7 E 8 or E 9 The signal for monitoring the min gas press...

Page 25: ...on bulletins BCU 46x and BCU 480 Parameters and values Application parameters Param eter No Parameter name Parameter value A001 Switch off threshold 1 2 20 A A002 Switch off threshold 2 2 20 A A003 Fl...

Page 26: ...A064 Flameless operation 0 Upon next burner start 1 Immediate burner start 2 Immediate switchover A067 Operating time in Manual mode 0 Unlimited 1 5 minutes A074 Combustion mode 0 Flame mode 1 menox...

Page 27: ...tFS2 0 25 Time in seconds Param eter No Parameter name Parameter value A101 Function of sensor 1 0 No function 1 APS Purge 2 APS Stage 1 3 APS Purge Stage 1 4 APS Stage 2 5 APS Purge Stage 2 6 APS Sta...

Page 28: ...arameter I050 for parameter values I054 Contact 85 86 87 function See parameter I050 for parameter values Param eter No Parameter name Parameter value I061 Function of input 1 0 Off 1 Sensor 1 2 Senso...

Page 29: ...rature 20 to 70 C 4 to 158 F no condensation permitted Storage temperature 20 to 70 C 4 to 158 F Transport temperature ambient temperature Enclosure IP 65 pursuant to IEC 529 Safety class 1 Pollution...

Page 30: ...d fuel handling sys tems EN 746 2 when used with fuels and oxidants The BCU 4 is suitable for continuous operation pur suant to EN 298 2012 12 Section 3 126 and for intermittent operation pursuant to...

Page 31: ...nt software can be downloaded from our Internet site at http www docuthek com To do so you need to register in the DOCUTHEK Opto adapter PCO 200 Including BCSoft CD ROM Order No 74960625 Connection pl...

Page 32: ...bsystem Type B to EN 61508 2 2010 Mode of operation High demand mode pursuant to EN 61508 4 2010 Mean probability of dan gerous failure PFHD 32 9 10 9 1 h on BCU 4xx F1 38 3 10 9 1 h on BCU 4xx F3 Mea...

Page 33: ...7610 Combustion Safeguards and Flame Sensing Systems Suitable for applications pursuant to NFPA 86 Directive on the restriction of the use of hazardous substances RoHS in China Scan of the Disclosure...

Page 34: ...office agent The addresses are available on the Internet or from Elster GmbH We reserve the right to make technical modifications in the interests of progress Elster GmbH Strotheweg 1 D 49504 Lotte B...

Reviews: