background image

9

5 Set up with the display and adjustment module PLICSCOM

OPTISOUND3020 C • Two-wire 4 … 20 mA/HART

62687-EN-190926

5  Set up with the display and adjustment 

module PLICSCOM

5.1  Insert display and adjustment module

The display and adjustment module can be inserted into the sensor 

and removed again at any time. It is not necessary to interrupt the 

voltage supply.
Proceed as follows:
1.  Unscrew the housing lid
2.  Place the display and adjustment module in the desired position 

on the electronics (you can choose any one of four different posi-

tions - each displaced by 90°)

3.  Press the display and adjustment module onto the electronics 

and turn it to the right until it snaps in

4.  Screw housing lid with inspection window tightly back on
Disassembly is carried out in reverse order.
The display and adjustment module is powered by the sensor, an ad-

ditional connection is not necessary.

Fig. 6: Insert display and adjustment module

Note:

If you intend to retrofit the instrument with a display and adjustment 

module for continuous measured value indication, a higher lid with an 

inspection glass is required.

Mount/dismount display 

and adjustment module

Summary of Contents for OPTISOUND3020 C

Page 1: ...OPTISOUND3020 C Quick setup guide Ultrasonic Level Transmitter Two wire 4 20 mA HART...

Page 2: ...7 4 2 Wiring plan single chamber housing 8 4 3 Wiring plan double chamber housing 8 5 Set up with the display and adjustment module PLICSCOM 9 5 1 Insert display and adjustment module 9 5 2 Setup ste...

Page 3: ...ty and persons or environmental contamination can result Also the protective characteristics of the instrument can be impaired 1 4 General safety instructions This is a state of the art instrument com...

Page 4: ...E marking we confirm the conformity of the instrument with these directives The EU conformity declaration can be found on our homepage 1 7 Fulfillment of NAMUR recommendations NAMUR is the automation...

Page 5: ...onfiguration The type label contains the most important data for identification and use of the instrument Instrument type Article and serial number device Article number documentation Technical data A...

Page 6: ...plane the so called dead zone in which measurement is not possible is maintained The exact value of the dead zone is stated in chapter Technical data 1 2 Fig 1 Minimum distance to the max level 1 Dea...

Page 7: ...e sensor through the cable entry 6 Lift the opening levers of the terminals with a screwdriver see following illustration 7 Insert the wire ends into the open terminals according to the wir ing plan F...

Page 8: ...6 4 2 Wiring plan single chamber housing I2C Display 1 1 2 5 6 7 8 Fig 4 Wiring plan single chamber housing 1 Voltage supply signal output 4 3 Wiring plan double chamber housing I2C 1 1 2 Fig 5 Wiring...

Page 9: ...on on the electronics you can choose any one of four different posi tions each displaced by 90 3 Press the display and adjustment module onto the electronics and turn it to the right until it snaps in...

Page 10: ...menu item Medium the medium of your applica tion for example Aqueous solution Medium Liquid 4 Select in the menu item Application the vessel the application and the vessel form for example Storage ta...

Page 11: ...el walls cause interfering reflections which can impair the measurement A false echo storage detects and marks these false echoes so that they are no longer taken into account for the level measuremen...

Page 12: ...atic Information Depending on the version and application the highlighted menu windows may not always be available Basic adjustment Basic adjustment 1 Display Diagnostics Service Info Min adjustment 1...

Page 13: ...adjustment 4 Display Diagnostics Service Info False signal suppression 4 1 Change now Extended setting 4 2 None Current output 4 3 Characteristic 4 20 mA Fail mode 3 6 mA Min current 3 8 mA Simulatio...

Page 14: ...5 ft Bulk solids up to 3 5 m 11 48 ft Dead zone 0 4 m 1 312 ft Electromechanical data Cable entry Single chamber housing 1 x cable gland M20 x 1 5 cable 5 9 mm 1 x blind plug M20 x 1 5 or 1 x closing...

Page 15: ...15 Notes OPTISOUND3020 C Two wire 4 20 mA HART 62687 EN 190926...

Page 16: ...rs Vortex flowmeters Flow controllers Level meters Temperature assemblies Pressure transmitters Analysis products Products and systems for the oil and gas industry KROHNE Messtechnick GmbH Co KG Ludwi...

Reviews: