Hazardous area supplement to the QuickStart
OPTIFLUX
10
4.2
Non-EEx I signal I/O
connections
The following non-intrinsically safe signal inputs/outputs are available:
I/O PCB
input/output functions,
Un < 32 V DC, In < 100 mA
Um = 253 V
Basic I/O
Current Output active and passive, with HART
Status Output / Control Input
Status Output
Pulse / Status Output
Modular I/O
Current Output, active or passive, with HART
Pulse / Status Output, active or passive, highC or Namur
Modular carrier with 1 or 2 I/O
modules
each module: 1 out of following 3 in/output functions:
•
Current Output, active or passive
•
Status / Pulse Output, active or passive, highC or Namur
•
Control Input, active or passive, highC or Namur
Profibus DP I/O
Profibus-DP, active
Fieldbus I/O
Profibus-PA or
Foundation Fieldbus
•
The options separated with slash “/” are software selectable (can be changed by user)
•
The options separated by the word “or” are hardware versions (must be ordered as such)
•
All outputs are passive unless otherwise indicated
•
HighC means High Current input/output, Namur means input/output to Namur recommendations