2
DEVICE DESCRIPTION
18
OPTIBAR 5060
www.krohne.com
04/2021 - 4003591803 - AD OPTIBAR 5060 Exia R03 en
OPTIBAR * 5060 VGK5/6/D*A/W/V C/U/0/H/T with integrated electronics P (Profibus PA),
F (Foundation Fieldbus)
Display and adjustment circuits:
(terminals 5, 6, 7, 8)
3
,
4
In protection type intrinsic safety Ex ia IIC
For connection to the intrinsically safe circuit or for
connection of an OPTIBAR * 5060 VGK5/6/D*A/W/V C/U/0/H/T
with integrated electronics S or T for electronic differential
pressure measurement.
The rules for interconnecting intrinsically safe circuits
between
OPTIBAR * 5060 VGK5/6/D*A/W/V C/U/0/H/T and
OPTIBAR * 5060 with electronics S or T are observed when the
overall inductance and overall capacitance of the connecting
cable between
OPTIBAR * 5060 VGK5/6/D*A/W/V C/U/0/H/T and
OPTIBAR * 5060 with electronics S or T
L
cable
= 212
H and C
cable
= 1.98
F are not exceeded.
Take into account the following cable inductances L
i
and cable
capacitances C
i
when using the supplied connection cable
between OPTIBAR * 5060 VGK5/6/D*A/W/V C/U/0/H/T and
OPTIBAR * 5060 with electronics S or T.
•
L
i
= 0.62
H/m
•
C
i wire/wire
= 150 pF/m
•
C
i wire/shield
= 270 pF/m
3
In the "Ex-i" electronics compartment for OPTIBAR in version with single chamber housing A, K, V or 8.
4
In the "Ex-i" terminal compartment for OPTIBAR in version with double chamber housing D, W or R.
Table 2-14: Electrical data for OPTIBAR * 5060 with integrated electronics P or F
Intrinsically safe circuit for the display and adjustment module
OPTIBAR * 5060 VGK5/6/D*A/W/V C/U/0/H/T with integrated electronics P (Profibus PA),
F (Foundation Fieldbus), version with single chamber housing A, K, V or 8
Circuit for the display and adjustment
module: (spring contacts in the "Ex-i"
electronics compartment)
In protection type intrinsic safety Ex ia IIC
Only for connection to the display and adjustment module.
Table 2-15: Intrinsically safe circuit for the display and adjustment module
OPTIBAR * 5060 with integrated electronics P or F with single chamber housing A, K, V or 8