TECHNICAL DATA
8
73
H250
www.krohne.com
04/2009 - 4000269302 MA H250-R02
Indicator M10
Indicator M10
Indicator M10
Indicator M10
M10 cable gland
(Standard)
without
M20 x 1.5
On request
M 20x1.5 Ex d
On request
M10 current output
Terminal connection
2.5 mm
2
Power supply
24 VDC
±
30%
Min. power supply for HART
®
18 VDC
Measuring signal
4.00...20.00 mA = 0...100% flow value in 2-wire technology
Power supply influence
< 0.1%
Dependence on external resistance
< 0.1%
Temperature influence
< 5
µ
A/K
Max. external resistance / load
≤
630 Ohm
Min. load for HART
≥
250 Ohm
Software firmware version
02.17
Ident No.
3209470500
M10 HART
®
Manufacturer name (code)
KROHNE Messtechnik (69 = 45h)
Model name
M10 (234 = EA)
HART
®
protocol revision
5.9
Device revision
1
Physical layer
FSK
Device category
Transmitter
M10 process variable
Values [%]
Signal output [mA]
Over range
+105 (
±
1%)
20,64...20.96
Device error identification
> 110
> 21.60
Maximum
112.5
22
Multidrop operation
-
4.5
Lift-off voltage
12 VDC