Operating Instructions
19
7
PLATE HEAT EXCHANGER (OPTION)
Cleaning of plate exchanger
Soldered heat exchanger:
For the removal of lime- and rust deposits, purifying agent SWEPcip AS, RS,
CS or S (according to material) is suitable. Cleaning may be performed by means of SWEP cleaning
device C.I.P 90 (circulation method) or a stationary pump.
Screwed heat-exchanger:
In this case the heat exchanger can also be disassembled for cleaning.
See attached concept for further technical data.
Stainless steel
Lime
Rust
Lime + Rust
SWEPcip AS
SWEPcip CS
SWEPcip AS
Max. Temp:
80 °C
80 °C
80 °C
Max. time:
8 h
8 h
8 h
Mixture ratio:
1:10
1:5
1:10
Steel
Lime
Rust
Lime + Rust
SWEPcip AS
SWEPcip RS
SWEPcip S
Max. Temp:
80 °C
80 °C
50 °C
Max. time:
8 h
8 h
8 h
Mixture ratio:
1:10
1:5
1:5
8
Waste disposal
The refrigerant cycle of the chiller contains an enviroment friendly refrigeration fl uid. Only registered and
qualifi ed refrigeration companies are permissible to carry out work on the chiller. Before attending any
repairments or maintanance work on the refrigeration cycle the refrigerant must be recovered by means of
a recovery unit. Any intention blowing off the refrigerant is prohibited. Disposal of the refrigerant and any
other parts like compressor oil or waste water must be completed according to local regulations only.
Specifi cation subject to change.