INSTALLATION INSTRUCTIONS
6.1
SAFETY INSTRUCTIONS
WARNING!
This product contains dangerous voltage that when touched can cause electric shock,
burns or death. Protective earth must always be connected in a reliable way to avoid the risk of
live parts in the equipment in the event of faults. No live parts are permitted during installation.
The product must be installed by qualified personnel (see
) section.
WARNING!
Check both before and after setting-up that the equipment does not have any
mechanical damage. Check that the equipment and individual rectifier modules have the intended
rated voltage. Cables for input and output power must be correctly dimensioned to avoid fire
hazard.
6.2
GENERAL
Installation of the parts that belong to the monitoring unit are not dealt with in this manual. For
complete installation instructions these instructions should therefore be used in combination with
the installation instructions included in the
Manual for monitoring unit PCM2
.
6.3
STORAGE AND PROTECTION
Storage is to be in a dry area and at a temperature that does not exceed the -40 to +70 °C range.
6.4
MOUNTING
The equipment is designed for wall mounting indoors in a room that is dry, clean and free from
conductive dust. In order to guarantee free air flow for all ventilation openings, at least 40 mm of
free space should be left on each side and at least 100 mm on the bottom of the equipment.
Temporarily removing the rectifier modules facilitates assembly considerably, partly through better
accessibility, and partly through substantially lower weight.
The rear plate of the equipment has four mounting holes shaped as keyholes. In order to fit the key
hole, the screw should have a diameter of a max of 6 mm and the screw head diameter 9.5 - 13.5
mm. See also dimension diagram
WARNING!
The equipment may cause personal injury or damage to property if dropped. Use
secure lifting aids where appropriate. Make sure the mounting screws and their attachments to the
wall can easily and safely handle the weight of the equipment.
6.5
ELECTRICAL INSTALLATION
6.5.1
General
The equipment is designed for permanent installation. Protective earth must
be connected before any other installation
For cable inlets there are six “knock-out” holes of which one has a diameter
of 37 mm designed for fitting type PG29 and five with a diameter of 22.5 mm
designed for fitting type PG16.
In order to increase accessibility and thereby facilitate installation, it is