SLD/DLD/PLD AIR COOLED CONDENSING UNITS
8
SYSTEM
CAPACITY
BTU/H
+20° F
Equivalent Suction Line Length
-20° F
Equivalent Suction Line Length
Liquid Line
Receiver to Expansion Valve
25'
50'
75'
100'
25'
50'
75'
100'
25'
50'
75'
100'
R-22
36,000
7/8
1 1/8
1 1/8
1 3/8
1 1/8
1 3/8
1 3/8
1 3/8
3/8
1/2
1/2
1/2
42,000
7/8
1 1/8
1 1/8
1 1/8
1 1/8
1 3/8
1 3/8
1 5/8
3/8
1/2
1/2
1/2
48,000
7/8
1 1/8
1 1/8
1 1/8
1 1/8
1 3/8
1 3/8
1 5/8
1/2
1/2
1/2
1/2
54,000
1 1/8
1 1/8
1 1/8
1 3/8
1 3/8
1 3/8
1 5/8
1 5/8
1/2
1/2
1/2
1/2
60,000
1 1/8
1 1/8
1 1/8
1 3/8
1 3/8
1 3/8
1 5/8
1 5/8
1/2
1/2
1/2
1/2
66,000
1 1/8
1 1/8
1 3/8
1 3/8
1 3/8
1 5/8
1 5/8
1 5/8
1/2
1/2
5/8
5/8
72,000
1 1/8
1 3/8
1 3/8
1 3/8
1 3/8
1 5/8
1 5/8
2 1/8
1/2
1/2
5/8
5/8
78,000
1 1/8
1 3/8
1 3/8
1 3/8
1 3/8
1 5/8
1 5/8
2 1/8
1/2
1/2
5/8
5/8
84,000
1 1/8
1 3/8
1 3/8
1 3/8
1 3/8
1 5/8
2 1/8
2 1/8
1/2
5/8
5/8
5/8
90,000
1 1/8
1 3/8
1 3/8
1 5/8
1 3/8
1 5/8
2 1/8
2 1/8
1/2
5/8
5/8
5/8
120,000
1 3/8
1 3/8
1 5/8
1 5/8
1 5/8
2 1/8
2 1/8
2 1/8
5/8
5/8
5/8
7/8
150,000
1 3/8
1 5/8
1 5/8
2 1/8
2 1/8
2 1/8
2 1/8
2 5/8
5/8
7/8
7/8
7/8
180,000
1 3/8
1 5/8
1 5/8
2 1/8
2 1/8
2 1/8
2 5/8
2 5/8
5/8
7/8
7/8
7/8
210,000
1 5/8
2 1/8
2 1/8
2 1/8
2 1/8
2 5/8
2 5/8
2 5/8
5/8
7/8
7/8
7/8
240,000
1 5/8
2 1/8
2 1/8
2 1/8
2 1/8
2 5/8
2 5/8
2 5/8
5/8
7/8
7/8
7/8
300,000
2 1/8
2 1/8
2 1/8
2 5/8
2 1/8
2 5/8
3 1/8
3 1/8
7/8
7/8
1 1/8
1 1/8
360,000
2 1/8
2 1/8
2 5/8
2 5/8
2 5/8
2 5/8
3 1/8
3 1/8
7/8
7/8
1 1/8
1 1/8
480,000
2 1/8
2 5/8
2 5/8
2 5/8
7/8
1 1/8
1 1/8
1 1/8
600,000
2 1/8
2 5/8
3 1/8
3 1/8
7/8
1 1/8
1 1/8
1 3/8
720,000
2 5/8
3 1/8
3 1/8
3 1/8
7/8
1 1/8
1 1/8
l 3/8
840,000
2 5/8
3 1/8
3 1/8
3 5/8
1 1/8
1 1/8
1 3/8
1 3/8
960,000
2 5/8
3 1/8
3 1/8
3 5/8
1 1/8
1 3/8
1 3/8
1 3/8
Line sizes which are shaded indicate the maximum suction line size which may be used for a riser. In no case should the riser
exceed the horizontal line size. Properly placed suction traps must be used to insure proper oil return.
TABLE 1B
RECOMMENDED LINE SIZES FOR R-404A and R-507
SUCTION LINE SIZE