#BIR-20-L R.5 June 2020
Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
VENTING
23
6.4 Vertical Terminations
NOTE: Attic insulation shields may be insulated using unfaced
insulation products listed as non-combustible per ASTM E 136.
The vent configurations listed below are shown with rigid pipe.
Flexible pipe may be used for approved venting configurations by vent
manufacturers listed in Section 6.1 Approved Vent Systems on page
21.Refer to vent manufacturer’s instructions.
Minimum / Maximum Vertical Venting:
3’ (914mm) minimum vertical length / 50’ (15.24m) maximum vertical
termination cap
Table 6.2, Recommended Restriction for Vertical Terminations
Fuel
Vent
Configurations
Baffle Positions
Restrictor Setting
Natural Gas
Minimum
Vertical
Setting (5)
Install Restrictor
Remove knockout(s)
Natural Gas
Maximum
Vertical
Setting (5)
Install Restrictor
Remove knockout(s)
Propane
Minimum
Vertical
Setting (5)
Install Restrictor
Remove knockout(s)
Propane
Maximum
Vertical
Setting (5)
Install Restrictor
Remove knockout(s)
DIAG.1 VERTICAL TERMINATIONS
36”
(914mm)
50’
(15.24m)
VERTICAL
TERMINATION CAP