Filter Removal and Service

Kooltronic Heat Exchanger feature an easily removable inlet filter to
facilitate necessary cleaning.

1)

Move the filter forward, using attached tab, to clear the
near filter retainer.  Pull the filter downward and toward you until the 
far side of the filter clears the far filter retainer.

2)

After removal, the filter should be flushed under warm running water 
with the clean side up, driving contaminants out the dirty side of the 
filter.  If the accumulated dirt is oily, washing in a detergent bath is 
recommended, followed by warm water rinse as above.

3)

The filter may be sprayed with 

Kooltronic A-16 Filter Recoating 

Adhesive

to trap fine airborne contaminants, or they can simply 

be dried and reinstalled as strainer type filters. 

Recoating

is recommended for the best results.

4)

Reinstall the filter:  (a) Holding the tab, slide the filter into the near 
retainer, (b) press filter against the unit and (c) slide forward into
far retainer.

CAUTION

Do not operate the Heat Exchanger for extended periods

of time with the filter removed.  The heat exchanger element

may become clogged with dust or lint from the ambient

environment.  A clogged heat exchanger element is not 

readily detected and will give the same reaction as clogged

filter.  A clean filter is the best protection.

VIII. Packing Procedure

Keep Heat Exchanger in proper upright position.

Pack Heat Exchanger in an appropriate carton (preferably original carton if possible),
with adequate internal protective packaging, making sure carton is marked properly.

For local controlled transportation, strap carton where possible, to a secure part of
truck to prevent falling or sliding, minimizing vibration, etc.

For common carrier shipment, band unit(s) securely to a pallet.  Unpalletized ship-
ment risks severe damage which voids the warranty.

CAUTION

Disconnect electric power from the Heat Exchanger

before proceeding.

Summary of Contents for TRIMLINE KXNP Series

Page 1: ...HEAT EXCHANGER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 046 05 12 18 CDR 20111 Find additional information on this model at kooltronic com or use the Technical Documents QR code below Technical Documents ...

Page 2: ...c TrimLine Heat Exchangers are designed for indoor applications with ambient temperatures from 50 F to 131 F and maximum allowable enclosure temperature of 160 F These heat exchangers utilize a counterflow airstream for maximum heat transfer efficiency in a closed loop system providing cooling within sealed electronic cabinets This Manual provides you with the necessary general information for pro...

Page 3: ...signee s failure to file a timely freight claim III Product Handling Do not attempt to operate your Kooltronic Heat Exchanger until you read and thoroughly understand this Manual Before operating this unit all electrical wiring must be checked to assure the proper connections IV Product Identification and Nameplate Each Kooltronic Heat Exchanger includes an identification nameplate This nameplate ...

Page 4: ... TAB You can locate your cutout anywhere within this opening Locate your cutout close to the top and not less than 4 high Make sure the cutouts don t interfere with components inside your cabinet 4 Mount the M TAB to the outside of the cabinet using all the mounting hardware supplied by Kooltronic 1 4 20 screws nuts washers Preferred positions one in each corner and two near center on each side NO...

Page 5: ... 18 12 135 16 101 8 7 12 KXNP59 171 16 71 2 215 16 151 4 277 8 20 14 1411 16 11 611 16 16 Technical Data 60 Hz operation For 50 Hz operation consult Kooltronic KXNP33 115AC 2 60 227 160 131 33 58 56 K2XNP33 230AC 1 90 227 160 125 33 58 56 K7XNP33 24BLDC 10 00 240 160 131 33 58 56 K8XNP33 48BLDC 5 80 270 160 131 33 58 56 KXNP36 115AC 3 20 363 160 131 42 75 67 K2XNP36 230AC 1 60 363 160 131 42 75 67...

Page 6: ...7121F 0744 24A K2XNP47 0452 03 0261 54 17121F 0744 24A K7XNP47 0263 05 17121F 0744 24A K8XNP47 0263 06 17121F 0744 24A KXNP59 0452 03 0261 287 22501F 0744 25A K2XNP59 0452 03 0261 288 22501F 0744 25A VII Maintenance Kooltronic Air Cooled Heat Exchangers are designed to require only routine cleaning of air filters and the heat exchanger element to assure unimpeded airflow through the heat exchanger...

Page 7: ...e tab slide the filter into the near retainer b press filter against the unit and c slide forward into far retainer CAUTION Do not operate the Heat Exchanger for extended periods of time with the filter removed The heat exchanger element may become clogged with dust or lint from the ambient environment A clogged heat exchanger element is not readily detected and will give the same reaction as clog...

Page 8: ...s received by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a suitable container for shipment preferably the original packaging if available All Heat Exchangers must be returned in an upright position properly secured to a pallet Improper packaging may void wa...

Reviews: