background image

Keep This  Manual

With Air Conditioner

AIR CONDITIONER

OPERATOR'S MANUAL

CAUTION

BEFORE INSTALLING AND

USING THIS AIR CONDITIONER,

IT IS IMPORTANT THAT THIS

MANUAL BE READ AND

UNDERSTOOD THOROUGHLY

KOOLTRONIC, INC.

30 Pennington-Hopewell Road

Pennington, NJ 08534

609 • 466-3400

FAX: 609 • 466-1114

www.kooltronic.com

900-039-41 (2/19)
(CDR: 20131)

TRIMLINE

KA4C6NP47-1 

Summary of Contents for TRIMLINE KA4C6NP47-1

Page 1: ...ON BEFORE INSTALLING AND USING THIS AIR CONDITIONER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 6...

Page 2: ...n Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes of electronics enclosures in...

Page 3: ...ate in a horizontal position only This placement must be done a minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before opera...

Page 4: ...ements y Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent dam...

Page 5: ...ed through the condenser coil where it absorbs the heat and is then discharged to the environment The unit is equipped with a Bypass Thermostat to prevent the evaporator coil from freezing and elimina...

Page 6: ...delayed until the system pressures rise 10 Operate the air conditioner for approximately ten 10 minutes During this period no unusual noise or vibration should be evident Both the evaporator and cond...

Page 7: ...M TAB by sliding the studs located on each side panel into the slots on the M TAB 6 Insert the remaining 10 32 screws and seal washers supplied by Kooltronic through the air conditioner side panel and...

Page 8: ...25 1200 2 Drawings and Dimensions NP47 SERIES Dimensions inches metric are for reference only and are subject to change FILTERED CONDENSER AIR INLET Ambient Air In CONDENSER OUTLET Warm Ambient Air O...

Page 9: ...lower Assembly 6015 00 11 Filter 12251F Technical Data KA4C6NP47 1 6000 125 50 115 100 60 50 16 5 150 160 Switchable Switch is internally mounted for security Rating shown is for operation at maximum...

Page 10: ...ng Schematic SOLENOID VALVE GN S C R WE SUPPRESSOR O L CAP CAP 1 3 EVAP BLOWER MOTOR MOTOR BLOWER COND START RELAY S L 2 1 M CAP COMPR 6 8 RELAY T STAT 70 BU Y R T STAT 75 Y BU R BK BYPASS WD 872 KA4C...

Page 11: ...off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable inle...

Page 12: ...e air conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect refrigerant leaks during and after manufacture It is...

Page 13: ...applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Blower Replace Evaporator Blower Mo...

Page 14: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Reviews: