background image

3

II. Incoming Inspection

Kooltronic Air Conditioners are designed, built and packaged to withstand the shock and vibration normally
associated with shipment by common carriers. Occasionally improper handling during shipping causes damage.
Such handling could include unbanding of palletized shipments, failing to respect 

"This Side Up"

arrows, rough

handling, falling off conveyors, excessive vibration, crushing, etc. Therefore, a thorough inspection should be
done upon receipt of all shipments. Any carton tears, dents, scratches, loose articles or evidence of oil are signs
of damage and should be noted on the Freight Bill. Cartons should be opened promptly and the units inspected
for CONCEALED DAMAGE. Kooltronic Air Conditioners must be delivered in the proper mounting position to
assure that damage to the compressor has not occurred during shipping. Any Kooltronic Air Conditioner that is
delivered removed from the banded pallet, lying down or double stacked should be refused.

An immediate claim MUST be filed with the freight carrier and an inspection requested. Retain all packing
materials. Kooltronic cannot assume responsibility for Consignee's failure to file a timely freight claim.

III. Product Handling:

1) Do not attempt to operate your Kooltronic Air Conditioner until you read and thoroughly understand this

Manual. See section

VI PRE-INSTALLATION TESTING.

2) Before operating the Kooltronic Air Conditioner be certain that it is placed in its correct mounting position.

All Air Conditioners containing an MM, NM, P, or V as part of the model number are designed to
operate in a vertical position only. All Air Conditioners containing an H, RT or RM in the model
number are designed to operate in a horizontal position only.

This placement must be done a minimum

of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area. 

CAUTION

3) Before operating this unit, all electrical wiring must be checked to assure the proper connection to the

correct power source. Minimum circuit ampacity should be at least 125% of the amperage found on the air
conditioner label for the corresponding voltage. Do not exceed the maximum fuse size found on the label.

4) We do not recommend that Air Conditioners be shipped to their final destination attached to an enclosure.

In the event that the Air Conditioner needs to be shipped attached to an enclosure it is strongly
recommended that proper support be provided for the Air Conditioner. Excessive vibration can occur if Air
Conditioners are not properly supported when shipped on enclosures, increasing the potential for internal
damage and voiding the warranty.

5)

PROCEDURE FOR PROPER PACKING AND SHIPMENT OF KOOLTRONIC AIR
CONDITIONERS:

Keep Air Conditioner in proper upright position indicated by arrow markers.

Pack Air Conditioner in an appropriate carton (preferably original carton if possible), with
adequate internal protective packaging, making sure carton is marked and is kept in correct
upright position.

For local, controlled transportation, strap carton to a secure part of truck to prevent falling or
sliding, minimize vibration, etc.

For common carrier shipment, band unit(s) securely to a pallet. Unpalleted shipment risks
severe damage which voids the warranty.

Kooltronic Air Conditioners must be operated in their proper mounting position. If attempts are

made to operate a unit that is not in its designed mounting position, permanent compressor

damage will occur. This action will void the warranty. To avoid compressor damage do not tip the

unit more than 45° from its proper mounting position.

Summary of Contents for Trimline 13NP47 Series

Page 1: ...ON BEFORE INSTALLING AND USING THIS AIR CONDITIONER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 034 10 2 19 CDR 20131 TRIMLINE 13NP47 SERIES ...

Page 2: ...ction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes of electronic enclosures in capacities ranging from 1 000 to 30 000 BTU H Our closed loop design also ensures that your components will not be exposed to hot dirty operating conditions This Manual provides you with the neces...

Page 3: ...rate in a horizontal position only This placement must be done a minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection to the correct power source Minimum circuit ampacity should be at least 125 of the amperage found on the air condi...

Page 4: ...rements y Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to the unit ALL MOTORS ARE THERMALLY PROTECTED VIOLATES WARRANTY UNAUTHORIZED SERVICE OR MODIFICATION COMPARTMENT ONLY NEMA EEMAC UL50 BY UNDERWRITERS LABORATORIES INC TYPE 1 SPECIAL PURPOSE AIR ...

Page 5: ...t air through the drain tube or the condensate evaporator The heat removed through the evaporator coil is transferred by the compressed refrigerant to the condenser coil Ambient air or water is then passed through the condenser coil where it absorbs the heat and is then discharged to the environment The EPR Evaporator Pressure Regulator valve prevents the evaporator coil from freezing by reducing ...

Page 6: ...ical supply leaving electrical power to the unit turned off 3 Note the factory thermostat setting which is 75o F 4 Turn the electrical power on 5 Verify that the evaporator blower or fan is running 6 Verify that the condenser blower or fan is running 7 Operate the air conditioner for approximately ten 10 minutes During this period no unusual noise or vibration should be evident Both the evaporator...

Page 7: ...Mount the unit to the M TAB by sliding the studs located on each side panel into the slots on the M TAB 6 Insert the remaining 10 32 screws and seal washers supplied by Kooltronic through the air conditioner side panel and into the M TAB To avoid misalignment of parts do not tighten any of the screws until they are all installed Be careful not to overtighten the screws 7 The drain hose must not be...

Page 8: ...TYP 15 12 384 0 18 00 457 2 12 50 317 5 3 00 76 2 12 88 327 1 12 24 310 8 47 26 1200 4 17 28 438 9 15 56 395 2 RIGHT SIDE BACK BOTTOM TOP LEFT SIDE FRONT 12 00 304 8 Drawings and Dimensions 13NP47 SERIES Dimensions inches metric are for reference only and are subject to change GA49100A Rev B ...

Page 9: ... Weight Model 95 95 Max Min Volts Hz Amps Amps lbs Major Component Replacements KA3C13NP47R K2A3C13NP47R Part Part Number Part Number Compressor 0665 80 0665 81 Compressor Capacitor 0452 54 0452 32 Condenser Blower Motor 0194 103 0194 50 Condenser Blower Capacitor 0452 32 0452 06 Evaporator Blower Motor 0261 08 0261 54 Evaporator Blower Capacitor 0452 03 0452 03 Evaporator Coil 0666 29 0666 29 Con...

Page 10: ...115 V 230 V RELAY TO CUSTOMER ALARM SYSTEM COMPRESSOR O L 0 1 4 8 2 6 1 3 C R S CAP COND BLOWER MOTOR CAP OPTIONAL PRESSURE SWITCH START ASSIST 115 V ONLY TERMINAL BLOCK COOLING EFFECT DETECTOR COMMON RED BLUE YELLOW h RED TO YELLOW CLOSES ON TEMPERATURE INCREASE RED TO BLUE OPENS ON TEMPERATURE INCREASE BK WD 838 13NP47R ...

Page 11: ... off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable inlet filter to facilitate necessary cleaning CAUTION 1 Lift the filter using the attached tab to clear the lower filter retainer Pull filter toward you and downward until the top of the filter clears th...

Page 12: ...he air conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect refrigerant leaks during and after manufacture It is possible that shipping or other damage or microscopic leaks over a long period may result in the need for replenishment of refrigerant charge When it has been verified by a Certified EPA Technician ...

Page 13: ... applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Blower Replace Evaporator Blower Motor or Assembly Clogged Evaporator Coil Clean Coil Condensate draining Enclosure not properly sealed Check and seal all openings continuously Excessive opening of Enclosure Eliminate the frequency of...

Page 14: ...received by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a suitable container for shipment preferably the original packaging if available All Air Conditioners must be returned in an upright position properly secured to a pallet Improper packaging may void war...

Reviews: