background image

6

Major Component Replacements

KXHE240A

KXHE360A

KXHE125A

KXHE245

KXHE365

Ambient Blower Assembly

7083-00-13

7083-00-13

8050-00-33

8050-00-33

8060-00-11

Ambient Blower Motor

0261-08

0261-08

0261-08

0261-08

0261-287

Ambient Blower Capacitor

0452-03

0452-03

0452-06

0452-06

0452-03

Cabinet Blower Assembly

7083-00-13

7083-00-13

8050-00-33

8050-00-33

8060-00-11

Cabinet Blower Motor

0261-08

0261-08

0261-08

0261-08

0261-287

Cabinet Blower Capacitor

0452-03

0452-03

0452-06

0452-06

0452-03

Heat Exchanger Element

0744-13A

0744-14A

0744-17A

0744-16A

0744-15A

Filter

240F

240F

5251F

7001F

10501F

Above parts are for 115V units.  For 230V, consult factory.

VII. Maintenance

Kooltronic Air-Cooled Heat Exchangers are designed to require only routine cleaning
of air filters and the heat exchanger element to assure unimpeded airflow through the
heat exchanger element. It is not possible to recommend specific filter cleaning intervals
since the level and the nature of air borne particulate matter differs widely with each
installation. It is generally sufficient to remove and wash the reusable aluminum
mesh air filter when the outer surface of these filters appear covered with a thin layer
of dust or lint.  Filter recoating adhesive is recommended. Appropriate disposable
filters are available from Kooltronic.

If filter service is neglected or delayed, the heat exchanger will not perform at its design
capacity. The first indication of excessively clogged air filter is usually a gradual
increase of temperature within the equipment cabinet. Continued operation under
these conditions will cause damage, shorten blower motor life and void the warranty.

Filter Removal and Service

Kooltronic Heat Exchanger feature an easily removable inlet filter to
facilitate necessary cleaning.

CAUTION

Disconnect electric power from the Heat Exchanger

before proceeding.

Summary of Contents for KXHE240

Page 1: ...G AND USING THIS AIR CONDITIONER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 041 04 3 19 CDR 20146 Find additional information on this model at kooltronic com or use the Technical Documents QR code below Technical Documents ...

Page 2: ...Kooltronic Heat Exchangers are designed to provide a cool environment for your electronic or electrical components There are models to fit virtually all sizes and shapes of electrical or electronic enclosures Our closed loop design also ensures that your components will not be exposed to hot dirty operating conditions This Manual provides you with the necessary general information for properly ins...

Page 3: ...er until you read and thoroughly understand this Manual Before operating this unit all electrical wiring must be checked to assure the proper connections IV Product Identification and Nameplate Each Kooltronic Heat Exchanger includes an identification nameplate This nameplate provides CAUTION Operate this unit only on the proper voltages and frequencies as noted on the nameplate MODEL NO SERIAL NO...

Page 4: ...ieved VI Specific Model Data Mounting Panel Mounted Heat Exchangers are equipped with two vertical mounting rails Using these rails the units may be mounted to any available vertical surface on the enclosure Refer to page 5 for location of all mounting holes and cutouts Make sure cutouts do not interfere with components inside your cabinet Proper alignment of air inlets and outlets is essential fo...

Page 5: ...18 6 21 2 51 2 311 4 61 2 3 4 KXHE125 281 2 81 4 17 19 183 8 151 2 113 4 8 7 33 4 31 2 99 16 6 5 8 KXHE245 471 4 81 4 17 19 183 8 151 2 113 4 26 31 2 25 8 51 4 201 8 83 4 5 8 KXHE365 591 2 81 4 17 19 183 8 151 2 117 8 34 31 2 13 4 811 16 287 16 83 4 1 KXHE240 4 115 2 4 230 160 131 27 56 60 K2XHE240 4 230 1 9 230 160 131 27 56 60 KXHE360 4 115 2 4 230 160 131 55 90 80 K2XHE360 4 230 1 9 230 160 131...

Page 6: ... through the heat exchanger element It is not possible to recommend specific filter cleaning intervals since the level and the nature of air borne particulate matter differs widely with each installation It is generally sufficient to remove and wash the reusable aluminum mesh air filter when the outer surface of these filters appear covered with a thin layer of dust or lint Filter recoating adhesi...

Page 7: ...to the near retainer b press filter against the unit and c slide forward into far retainer CAUTION Do not operate the Heat Exchanger for extended periods of time with the filter removed The heat exchanger element may become clogged with dust or lint from the ambient environment A clogged heat exchanger element is not readily detected and will give the same reaction as clogged filter A clean filter...

Page 8: ...s received by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a suitable container for shipment preferably the original packaging if available All Heat Exchangers must be returned in an upright position properly secured to a pallet Improper packaging may void wa...

Reviews: