5
VI. Specific Model Data
Mounting
Kooltronic Heat Exchangers have been engineered to be installed easily. To avoid damaging your
Heat Exchanger, please read the following information before installation:
1.
Loosen the two screws on the bottom holding the Mounting Template and Assembly Bracket
(M/TAB) to the unit. Remove the M/TAB.
2.
See Figure 1 for proper orientation.Place the M/TAB flush against the outside of the cabinet
to locate cutouts and mounting holes.
3.
Make sure the cutouts don't interfere with components inside your cabinet.
4.
Mount the M/TAB to the outside of the cabinet using all the mounting hardware supplied by
Kooltronic (
1/4
-20 screws/nuts/washers). Preferred positions: one in each corner and two near
center on each side. NOTE: Make sure the screws are inserted with heads toward you. Tighten
nuts securely.
5.
Route the power cord through the top cut out in your cabinet. Mount the unit to the M/TAB by
sliding the slots on the bulkhead into the hooks on the M/TAB. After unit is in place, tighten 2
screws at bottom of unit. These two screws will force the M/TAB into studs on side panel for a
tight seal.
6.
Attach overflow drain hose supplied to the drain exit at the bottom of the unit. This hose must
not be elevated above the exit port. Improper mounting will impede the flow of condensate and
may cause internal malfunctions.
7. Attach supply line to 1/2" O.D. copper tubing Inlet on bottom of unit.
8. Attach discharge line to 1/2" O.D. copper tubing Outlet on bottom of unit.
Dimensions (inches) are for reference only and are subject to change.
1
2
CONDENSATE
DRAIN
WATER INLET
WATER OUTLET
M/TAB
10.95
[278.0]
12.50
[318.0]
30.02
[762.4]
(8) .281 [7.1]
DIA. HOLES
1
2
10.00
[254.0]
1.29
[32.7]
1.09
[27.7]
10.25
[260.4]
1.21
[30.7]
8.70
[221.0]
8.70
[221.0]
8.70
[221.0]
9.00
[228.6]
12.50
[317.5]
1.71
[43.5]
30.02
[762.4]
15.25
[387.0]
5.54
[140.7]
4.84
[122.9]
1.75
[44.4]
FIGURE 1
MOUNTING PLAN
WARM AIR RETURN FROM
ENCLOSURE
COOL AIR OUTLET
TO ENCLOSURE
1
2