background image

5

VI. Installation Instructions

The Guardian Series NEMA 4 or 4X Filter Fans have been engineered to be installed easily. These NEMA 4 or 4X
filter fans have been designed for indoor or outdoor use. Prior to mounting, refer the mounting drawings below
showing dimensions and locations of mounting holes and cutouts. Prior to cutting or drilling, make sure that cutouts
and mounting holes do not interfere with components inside the cabinet. 
When mounting your filter fan please keep the following in mind:

VII. Drawings and Dimensions

9.85

[250.1]

16.56

[420.6]

6.12

[155.4]

1.86

[47.2]

(4) 1/4" -20

CAGE NUTS

POWER

CORD

2.81

[71.4]

4.62

[117.3]

2.61

[66.3]

18.00

[457.2]

5.01

[127.2]

FILTER WITH

REMOVABLE 

GUARD

AIR OUT

AIR I

N

 6.12

 [155.4]

 

 4.62

 [117.3]

 7.12

 [180.8]

 (4) .312 [7.9]

 DIA. HOLES

 1.86

 [47.2]

 13.75

 [349.2]

 2.81

 [71.3]

 6.50

 [165.1]

 

 1.68

 [42.6]

 2.61

 [66.3]

 8.99

 [228.3]

D

imensions, inches[mm] are for reference only and subject to change

.

KNP60FL

Proper orientation of unit is filter at the bottom.

A minumum of 6 inches clearance from filter to the nearest surface is recommended.

Use neoprene washers provided.

Recommended torque of 35-in-lbs for proper gasket compression.

MOUNTING PLAN

Summary of Contents for KNP60FL

Page 1: ...1114 www kooltronic com 900 057 07 CAUTION BEFORE INSTALLING AND USING THIS FILTER FAN IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY Guardian Series KNP60FL NEMA 4 or 4X Filter Fans READ AND SAVE THESE INSTRUCTIONS Find additional information on this model at kooltronic com or use the Technical Documents QR code below Technical Documents ...

Page 2: ... VIII Specific Model Data 6 Technical Data Standard Features Replacement Filters Optional Filter Hood Assemblies IX Packing Procedure for Warranty Return 6 X Maintenance 7 XI Warranty 8 I Introduction This Manual provides you with the necessary general information for properly installing and operating Guardian Series Filter Fans Unit specific technical data and mounting instructions are presented ...

Page 3: ...eing switched on accidentally If service panel cannot be locked securely fasten a prominent warning device such as a tag to the panel WARNING TO REDUCE THE RISK OF FIRE ELECTRIC SHOCK OR INJURY OBSERVE THE FOLLOWING Installation work and electrical wiring must be done by qualified person s in accordance with all applicable codes and standards including fire rated construction When cutting or drill...

Page 4: ...d this Manual Before operating this unit all electrical wiring must be checked to assure the proper connections Use only on GFCI Protected Receptacles V Product Identification and Nameplate Each Filter Fan includes an identification nameplate This nameplate provides CAUTION Operate this unit only on the proper voltages and frequencies as noted on the nameplate Model Number Electrical Power Charact...

Page 5: ...ase keep the following in mind VII Drawings and Dimensions 9 85 250 1 16 56 420 6 6 12 155 4 1 86 47 2 4 1 4 20 CAGE NUTS POWER CORD 2 81 71 4 4 62 117 3 2 61 66 3 18 00 457 2 5 01 127 2 FILTER WITH REMOVABLE GUARD AIR OUT AIR IN 6 12 155 4 4 62 117 3 7 12 180 8 4 312 7 9 DIA HOLES 1 86 47 2 13 75 349 2 2 81 71 3 6 50 165 1 1 68 42 6 2 61 66 3 8 99 228 3 Dimensions inches mm are for reference only...

Page 6: ...nit Operating Approximate Frequency Imput Imput Airflow Temp ºF Weight Model Voltage Hz Amps Watts CFM Min Max lbs Standard Features Filter Integrated Fan Guards Integrated Sealing Gasket IP55 Filter Protection NEMA 4 or 4X Rating Maintained if used with provided filter Secure Mounting Stainless Steel Shell NEMA 4X models Baked Powder Finish UL CSA Shielded Ball Bearing Motors UL CUL Listed Replac...

Page 7: ...fans will not perform at design capacity The first indication of an excessively clogged filter is usually a gradual increase of temperature within the equipment cabinet Filter removal and service Kooltronic Guardian GuardianX NEMA 4 or 4X Series Indoor Outdoor Filter Fans feature an easily removable filter to facilitate necessary cleaning CAUTION 1 On the bottom of the unit pull the filter retaine...

Page 8: ...ceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a suitable container for shipment preferably the original packaging if available All Air Conditioners must be returned in an upright position properly secured to a pallet Improper packaging may void warra...

Reviews: