VII. Maintenance

Kooltronic Air-Cooled Heat Exchangers are designed to require only routine cleaning
of air filters and the heat exchanger element to assure unimpeded airflow through the
heat exchanger element.  It is not possible to recommend specific filter cleaning
intervals since the level and the nature of air borne particulate matter differs widely
with each installation.  It is generally sufficient to remove and wash the reusable alu-
minum mesh air filter when the outer surface of these filters appear covered with a thin
layer of dust or lint.  Filter recoating adhesive is recommended.  Appropriate dis-
posable filters are available from Kooltronic.
If filter service is neglected or delayed, the heat exchanger will not perform at its design
capacity. The first indication of excessively clogged air filter is usually a gradual
increase of temperature within the equipment cabinet.  Continued operation under
these conditions will cause damage, shorten blower motor life and void the warranty.

3

4

4.00

[101.6]

TYP.

(24) .250 [6.4]
DIA. HOLES

(6) .312 [7.9]
DIA. HOLES

UNIT MOUNTING PLAN

M-TAB MOUNTING PLAN

.87

[22.2]

1.15

[29.2]

3.13

[79.4]

11.50

[292.1]

8.00

[203.2]

2.17

[55.0]

3.12

[79.2]

11.50

[292.1]

5.12

[130.0]

3.86

[97.9]

2.68

[68.0]

8.00

[203.2]

.89

[22.5]

.99

[25.1]

4.25

[107.9]

4.25

[107.9]

4.25

[107.9]

4.25

[107.9]

4.25

[107.9]

4.00

[101.6]

1.00

[25.5]

3

4

11.50

[292.1]

11.50

[292.1]

5.12

[130.0]

3.86

[97.9]

10.50

[266.7]

.50

[12.7]

1.72

[43.7]

13.00

[330.2]

13.00

[330.2]

2.68

[68.0]

8.00

[203.2]

2.17

[55.0]

3.12

[79.2]

8.00

[203.2]

4.25

[107.9]

32.25

[819.2]

13.12

[333.2]

31.50

[800.1]

13.08

[332.3]

14.49

[368.1]

1

2

3

4

Dimensions (inches) are for reference only and are subject to change.

Technical Data**

** 60 Hz. operation. For 50 Hz. operation, consult Kooltronic.

KNHX32

115

1.50

160

160

131

21

42

70

KNHX32E

115

1.50

160

160

131

21

42

70

K2NHX32

230

1.10

260

160

131

21

42

70

K2NHX32E

230

1.10

260

160

131

21

42

70

Maximum Allowable            Performance

Approx.

Power

Temperature °F

Watts/°F

Weight

Model

Volts

Amps

Watts

Enclosure

Ambient

Air In

Air Out

(lbs.)

Figure 1

Drawings and Dimensions

WARM AIR RETURN FROM
ENCLOSURE

COOL AIR OUTLET 
TO ENCLOSURE

3

4

FILTERED CONDENSER
AIR INLET (Ambient Air In)

CONDENSER OUTLET
(Warm Ambient Air Out)

1

2

Summary of Contents for KNHX32 Series

Page 1: ...S HEAT EXCHANGER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 046 06 12 18 CDR 20111 Find additional information on this model at kooltronic com or use the Technical Documents QR code below Technical Documents ...

Page 2: ...c TrimLine Heat Exchangers are designed for indoor applications with ambient temperatures from 50 F to 131 F and maximum allowable enclosure temperature of 160 F These heat exchangers utilize a counterflow airstream for maximum heat transfer efficiency in a closed loop system providing cooling within sealed electronic cabinets This Manual provides you with the necessary general information for pro...

Page 3: ...er stand this Manual Before operating this unit all electrical wiring must be checked to assure the proper connections IV Product Identification and Nameplate Each Kooltronic Heat Exchanger includes an identification nameplate This nameplate provides CAUTION Operate this unit only on the proper voltages and frequencies as noted on the nameplate MODEL NO SERIAL NO MAX CABINET VOLTS FREQ PH AMPS TEM...

Page 4: ...d Air Cabinet Blower Heated Air Ambient Air In an Air to Air Heat Exchanger heat from air surrounding the components is removed by a specially designed heat transfer element before being routed back into the enclosure Optional bimetal thermostat is used as Cooling Effect Detector The thermostat contacts close at 130 F and open at 90 F Major Component Replacements KNHX32 KNHX32E Condenser Blower As...

Page 5: ... mounting studs installed on the heat exchanger side panels into the inclined slots of the M TAB 6 Carefully mark all mounting holes from the flanges of the heat exchanger to the cabinet wall All holes in the heat exchanger flange must be used to maintain the NEMA 4 rating 7 Remove the heat exchanger from the M TAB and drill 218 dia mounting holes in the cabinet Do not attempt to drill mounting ho...

Page 6: ...and void the warranty 3 4 4 00 101 6 TYP 24 250 6 4 DIA HOLES 6 312 7 9 DIA HOLES UNIT MOUNTING PLAN M TAB MOUNTING PLAN 87 22 2 1 15 29 2 3 13 79 4 11 50 292 1 8 00 203 2 2 17 55 0 3 12 79 2 11 50 292 1 5 12 130 0 3 86 97 9 2 68 68 0 8 00 203 2 89 22 5 99 25 1 4 25 107 9 4 25 107 9 4 25 107 9 4 25 107 9 4 25 107 9 4 00 101 6 1 00 25 5 3 4 11 50 292 1 11 50 292 1 5 12 130 0 3 86 97 9 10 50 266 7 5...

Page 7: ...e tab slide the filter into the near retainer b press filter against the unit and c slide forward into far retainer CAUTION Do not operate the Heat Exchanger for extended periods of time with the filter removed The heat exchanger element may become clogged with dust or lint from the ambient environment A clogged heat exchanger element is not readily detected and will give the same reaction as clog...

Page 8: ...s received by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a suitable container for shipment preferably the original packaging if available All Heat Exchangers must be returned in an upright position properly secured to a pallet Improper packaging may void wa...

Reviews: