background image

4

IV. Product Identification and Nameplate

Each Kooltronic Air Conditioner includes an identification nameplate. This nameplate provides:

q

Model Number

w

Serial Number

e

Electrical power characteristics

r

Maximum and minimum ambient operating temperatures

t

Cooling capacity

y

Type and amount of refrigerant required for recharging

u

Design Pressure

i

Maximum Fuse Size

o

Manufacturing Order Number

a

Filter Part Number

s

Underwriters Laboratories Inc. Listed or Recognized Marks and NEMA ratings

We recommend you copy this information from your unit.

qwo

When ordering parts, specify the Model Number, Serial Number & MFG. Order Number.

e

Before operating, be sure that the power source matches these requirements.

y

Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit.

Make sure that these parameters are met. Failure to do so may result in permanent damage to the unit.

ALL MOTORS ARE THERMALLY PROTECTED

VIOLATES WARRANTY

UNAUTHORIZED SERVICE OR MODIFICATION

OUTDOOR USE

COMPARTMENT ONLY

NEMA/EEMAC/UL50 BY UNDERWRITERS LABORATORIES, INC.

TYPE 3R SPECIAL PURPOSE AIR CONDITIONER EQUIPMENT

TYPE 4/4X INTERFACE TO THE ELECTRICAL ENCLOSURE ONLY

NEMA/EEMAC/UL50 BY UNDERWRITERS LABORATORIES, INC.

SPECIAL PURPOSE AIR CONDITIONER

     MAX. 
FUSE SIZE

HIGH

LOW

Oz.

REFRIGERANT

MAX.°F

MIN.°F

AMBIENT TEMP.

COOLING

ALLOW 5 MIN. BEFORE RESTARTING AFTER SHUTDOWN

Air Conditioner

DESIGN PRESSURE P.S.I.G.

MFG. ORDER NO.

KOOLTRONIC, INC.   PENNINGTON, NJ

MANUFACTURED BY:

COOLING BTU

F.L.A.

PH.

FREQ.

VOLTS

SERIAL NUMBER

MODEL NUMBER

FILTER P/N

SERVICE AIR FILTER REGULARLY

e

e

e

e

r

r

t

y

q

w

u

u

i

a

s

o

Summary of Contents for Integrity K NA4C4P32L Series

Page 1: ...THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com INTEGRITY SERIES K_NA4C4P32L KNA6C4P32L 9...

Page 2: ...model page of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtuall...

Page 3: ...s prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connectio...

Page 4: ...Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to t...

Page 5: ...nger The warm air inside the enclosure is drawn through the evaporator coil where it is cooled dehumidified and returned Any enclosure moisture accumulated on the evaporator coil is collected in the c...

Page 6: ...ower will be delayed until the system pressures rise 10 Operate the air conditioner for approximately ten minutes During this period no unusual noise or vibration should be evident Both the evaporator...

Page 7: ...ing the 4 mounting studs installed on the air conditioner side panels into the 4 inclined slots of the M TAB 6 Carefully mark all mounting holes from the flanges of the air conditioner to the cabinet...

Page 8: ...105 K2NA4C1P32R5 1000 125 0 230 50 6 5 105 KNA4C2P32R 2000 125 0 115 100 60 50 13 0 12 0 105 KNA4C2P32R56 2000 125 0 115 50 60 13 0 105 K2NA4C2P32R 2000 120 0 230 200 60 50 6 0 105 K2NA4C2P32R5 2000...

Page 9: ...d tab Push the filter toward the front and downward until the rear part of the filter clears the rear filter retainer 2 To replace the rear filter in the P32 series lift the filter using both sides of...

Page 10: ...ycle on and off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily re...

Page 11: ...mmended that the air conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect refrigerant leaks during and after ma...

Page 12: ...r Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator B...

Page 13: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...