VI. Pre-Installation Testing

 

Before mounting the air conditioner to the enclosure, test for proper operation. This will verify the shipping 
integrity of the system. Please follow the steps below prior to installation. 

  

 

 

CAUTION 

 
 
 
 

 

 1

. The unit must sit in an upright position at a minimum room temperature of 65°F to allow the system to 

warm-up. This is particularly important during winter months. 

 2. Refer to the nameplate for proper electrical voltage and current requirements. Connect the power cord 

to a properly grounded and fused electrical supply, leaving electrical power to the unit turned off. 

 3. Note the factory thermostat setting which is 70

o

F.  

 4. Turn the electrical power on.  

 5. Verify that the evaporator blower or fan is running. 

 6. Verify that the condenser blower or fan is running. 

 7. Observe the temperature on the digital display. The thermostat must be set a minimum of 10°F below 

this temperature for the compressor to operate (the factory setting is 75°F). Refer to page 6 for 
instructions on adjustment of the thermostat. 

 8. Operate the air conditioner for approximately ten (10) minutes. During this period no unusual noise or 

vibration should be evident. Both the evaporator and condenser fans or blowers should be delivering 
air through their respective discharge ports. The cool air discharged should be less than 70°F when 
the room temperature is between 70°F and 80°F. It is normal for the condenser blower to cycle on/off 
during this period.   

 9. Turn off the electrical power and disconnect the air conditioner from the power source.  

10. If a cover plug was removed to adjust the unit, be sure to replace it in order to maintain the integrity 

of the closed-loop airflow system.   

 

NOTE:

   Before shipment all Kooltronic Air Conditioners are subjected to a performance test. 

 

VII. Specific Model Data

 

 

Mounting

 

 

The Kooltronic Special Purpose Air Conditioners K2NA6C30EP56TR-BR have been engineered to be installed 
easily.  Prior to mounting, refer to pages 10 and 11 for the drawings showing dimensions and locations of mounting 
holes  and cutouts. Prior to cutting or drilling, make sure that cutouts and mounting holes do not interfere with 
components inside the cabinet. To avoid damaging your air conditioner, please read the following information 
before installation: 

 

  

1.   It is recommended that a lift truck be used for installation.

The air conditioner must be standing in its proper mounting position for a minimum of five 

(5) minutes prior to testing. Failure to follow this procedure will cause permanent damage to 

the compressor. To avoid compressor damage do not tip the unit more than 45° from its 

proper mounting position.

Summary of Contents for EP56 Series

Page 1: ...ONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 039 106 12 21 CDR 20369 INTREPID EP56 SERIES K2A6C30EP56TR BR Find additional information...

Page 2: ...fic model page of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtu...

Page 3: ...prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection...

Page 4: ...of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to the u...

Page 5: ...then discharged to the environment When the Kooltronic Air Conditioner is properly sized it should operate constantly and maintain 75 F to 115 F enclosure temperature depending on the ambient temperat...

Page 6: ...the new set point value push the SET key again or wait 10 seconds HOW TO CHANGE A PARAMETER VALUE To change a parameter s value operate as follows 1 Enter the Programming mode by pressing the SET plu...

Page 7: ...p code 7 0 65535 rEL Software release 0 rSE Real set point 0 onF on off key enabling ES PbC Kind of probe ntc Adr Serial address 1 1 247 HES Differential for energy saving 0 F 54 54 rrd Regulation res...

Page 8: ...should be delivering air through their respective discharge ports The cool air discharged should be less than 70 F when the room temperature is between 70 F and 80 F It is normal for the condenser bl...

Page 9: ...nditioner Hang the air conditioner on the hooks Before the lift truck lowers the air conditioner make sure that the hooks are located inside of the small cutouts on the front panel 4 Tighten the air c...

Page 10: ...4 163 7 11 38 289 1 7 37 187 2 17 75 450 8 18 57 471 7 53 75 1365 3 4 56 115 8 1 78 45 3 33 21 843 6 0 80 20 3 0 95 24 1 7 46 189 4 TYP 20 25 514 3 1 45 36 7 EP56T EP56B 3 4 3 375 9 5 DIA OPTIONAL MOU...

Page 11: ...WER CORD 1 1 2 2 EP56B EP56T 3 4 EP56T EP56B 3 4 57 04 1448 7 DRAIN K2A6C30EP56TR BR Dimensions inches mm are for reference only and are subject to change Drawings and Dimensions CONDENSER AIR INLET A...

Page 12: ...or Capacitor 0452111 Condenser Blower Motor 0261 274 Condenser Blower Capacitor 0452 04 Evaporator Blower Motor 0261 275 Evaporator Coil 0667 51 Condenser Coil 0666 59 01 Thermostat 0750 137 NOTE Part...

Page 13: ...ued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter and condenser coil service The rear panel must be removed in order to clean the filters Af...

Page 14: ...running Low Line Voltage Check Nameplate Voltage against supply Voltage Compressor and Condenser Blower do not run Return temperature is Failed Compressor Check Compressor wire connections above set...

Page 15: ...vaporator Clean Coil difference between return and Coil clogged supply air is less than 10 F Evaporator Blower Condenser Loss of Refrigerant Locate and repair leak Blower and Compressor are running Ic...

Page 16: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Reviews: