II. Incoming Inspection

 

Kooltronic Air Conditioners are designed, built and packaged to withstand the shock and vibration normally 
associated with shipment by common carriers. Occasionally improper handling during shipping causes damage. 
Such handling could include unbanding of palletized shipments, failing to respect 

"This Side Up"

 arrows, rough 

handling, falling off conveyors, excessive vibration, crushing, etc. Therefore, a thorough inspection should be 
done upon receipt of all shipments. Any carton tears, dents, scratches, loose articles or evidence of oil are signs 
of damage and should be noted on the Freight Bill. Cartons should be opened promptly and the units inspected 
for CONCEALED DAMAGE. Kooltronic Air Conditioners must be delivered in the proper mounting position to 
assure that damage to the compressor has not occurred during shipping. Any Kooltronic Air Conditioner that is 
delivered removed from the banded pallet, lying down or double stacked should be refused. 

An immediate claim MUST be filed with the freight carrier and an inspection requested. Retain all packing 
materials. Kooltronic cannot assume responsibility for Consignee's failure to file a timely freight claim. 

III. Product Handling:

 

1) Do not attempt to operate your Kooltronic Air Conditioner until you read and  thoroughly understand this

Manual. See section 

VI PRE-INSTALLATION TESTING.

2) Before operating the Kooltronic Air Conditioner be certain that it is placed in its correct mounting position.

This Air Conditioner is designed to operate in a vertical position only. 

This placement must be done

a minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor
sump area.

CAUTION

 

3) Before operating this unit, all electrical wiring must be checked to assure the proper connection to the correct

power source. Minimum circuit ampacity should be at least 125% of the amperage found on the nameplate
for the corresponding voltage. Do not exceed the maximum fuse size found on the nameplate.

4) We do not recommend that Air Conditioners be shipped to their final destination attached to an enclosure. In

the event that the Air Conditioner needs to be shipped attached to an enclosure it is strongly recommended
that proper support be provided for the Air Conditioner. Excessive vibration can occur if Air Conditioners are
not properly supported when shipped on enclosures, increasing the potential for internal damage and voiding
the warranty.

5)

PROCEDURE FOR PROPER PACKING AND SHIPMENT OF KOOLTRONIC AIR
CONDITIONERS:

Keep Air Conditioner in proper upright position indicated by arrow markers.

Pack Air Conditioner in an appropriate carton (preferably original carton if possible), with adequate
internal protective packaging, making sure carton is marked and is kept in correct upright position.

For local, controlled transportation, strap carton to a secure part of truck to prevent falling or
sliding, minimize vibration, etc.

For common carrier shipment, band unit(s) securely to a pallet. Unpalleted shipment risks
severe damage which voids the warranty.

Kooltronic Air Conditioners must be operated in their proper mounting position. If attempts are 

made to operate a unit that is not in its designed mounting position, permanent compressor 

damage will occur. This action will void the warranty. To avoid compressor damage do not tip the 

unit more than 45° from its proper mounting position.

Summary of Contents for E16A1554

Page 1: ...ION BEFORE INSTALLING AND USING THIS AIR CONDITIONER IT IS IMPORTANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX...

Page 2: ...age of the Kooltronic website I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all si...

Page 3: ...prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure the proper connection...

Page 4: ...ect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to the unit ALL MO...

Page 5: ...ure accumulated on the evaporator coil is collected in the condensate tray and released to the ambient air through the drain tube or the condensate evaporator The heat removed through the evaporator c...

Page 6: ...be delayed until the system pressures rise 10 Operate the air conditioner for approximately ten 10 minutes During this period no unusual noise or vibration should be evident Both the evaporator and co...

Page 7: ...r cord through the top cut out in your cabinet Mount the unit to the M TAB by sliding the 4 studs on the side panel into the 4 slots on the M TAB After unit is in place tighten 2 screws at bottom of u...

Page 8: ...INLET Ambient Air In NP28 only CONDENSER OUTLET Warm Ambient Air Out NP28 only WARM AIR RETURN FROM ENCLOSURE COOL AIR OUTLET TO ENCLOSURE Drawings and Dimensions NP28 SERIES Other drain outlets are...

Page 9: ...5 50 60 13 0 85 K2A4C3NP28L 3000 120 50 230 200 60 50 6 0 85 K2A4C3NP28L5 3000 125 50 230 50 6 5 85 KA4C4NP28L 4000 125 50 115 100 60 50 13 0 12 0 85 KA4C4NP28L56 4000 125 50 115 50 60 13 0 85 K2A4C4N...

Page 10: ...nd the compressor will continue to cycle on and off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic A...

Page 11: ...pass valve fails it is strongly recommended that the Air Conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect r...

Page 12: ...Control Replace Thermostat or Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Ap...

Page 13: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Reviews: