VII. Specific Model Data

Mounting

Kooltronic Air Conditioners have been engineered to be installed easily. To avoid damaging your Air
Conditioner, please read the following information before installation:

1.

Loosen two screws on the bottom of the unit.

2.

See Figure 1 for proper M/TAB orientation.Place the M/TAB flush against the outside of the
enclosure to locate cutouts and mounting holes.

3.

NOTE: The top cutout for the warm air return does not have to match the full 4.

8

7" opening on

the M/TAB. You can locate your cutout anywhere within this opening. Locate your cutout close
to the bottom and not less than 3" high. Make sure the cutouts don't interfere with components
inside your cabinet.

4.

Mount the M/TAB to the outside of the cabinet using all the mounting hardware supplied by
Kooltronic (

1/

4

-20 screws/nuts/washers). NOTE: Make sure the screws are inserted with heads

on M/TAB side. Tighten nuts securely.

5.

Route the power cord through the top cut out in your cabinet. Mount the unit to the M/TAB by
sliding the slots located on the front panel on the hooks of the M/TAB. 

6.

Tighten two screws on the bottom of the unit and seal the unit against the enclosure. 

7.

Attach overflow drain hose supplied to the drain exit in bottom of the unit. 

CAUTION

If the Air Conditioner is mounted to the cabinet door you must be sure

that the door hinges will support the additional weight of the Air

Conditioner. Also be certain that when the door is opened fully, the

cabinet does not become unbalanced. The actual weight of the unit can

be found in the performance specifications.

7

Dimensions (inches) are for reference only and are subject to change.

MOUNTING PLAN

1.59

[40.4]

TYP.

  (16) .281 [7.1]
  DIA. HOLES

HEATED AMBIENT
AIR OUT

AMBIENT AIR IN

WARM AIR RETURN
FROM ENCLOSURE

COOL AIR SUPPLY
TO ENCLOSURE

1.24

[31.5]

4.13

[104.9]

6.69

[169.9]

TYP.

14.00

[355.6]

  7.12
[181.0]

34.19

[868.4]

  7.75
[196.8]

1.84

[46.7]

14.69

[373.0]

FIGURE 1

Summary of Contents for Advantage RP52 Series

Page 1: ...TANT THAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com ADVANTAGE RP52 SERIES 900 039 34...

Page 2: ...ction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes of electronic enclosures...

Page 3: ...ate in a horizontal position only This placement must be done a minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before opera...

Page 4: ...Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure to do so may result in permanent damage to t...

Page 5: ...ambient air by the condenser blower If latent heat exceeds 25 of the total cooling capacity excess condensate is released to the ambient through the drain tube The heat removed through the evaporator...

Page 6: ...essor should start Units equipped with a Short Cycle Protector have a 3 minute delay from when the power is turned on until the compressor begins to operate 8 Verify that the condenser blower fan is r...

Page 7: ...re inserted with heads on M TAB side Tighten nuts securely 5 Route the power cord through the top cut out in your cabinet Mount the unit to the M TAB by sliding the slots located on the front panel on...

Page 8: ...1 356 0 18 28 464 2 15 96 405 3 52 56 1335 0 POWER CORD DRAIN 17 18 436 3 1 50 38 1 15 91 404 0 Drawings and Dimensions RP52 SERIES 8 Dimensions inches are for reference only and are subject to change...

Page 9: ...Number Compressor 0665 50 Compressor Capacitor 0452 54 Condenser Blower Motor 0261 80 Condenser Blower Motor Capacitor 0452 06 Evaporator Blower Motor 0261 54 Evaporator Blower Motor Capacitor 0452 0...

Page 10: ...K COOLING EFFECT DETECTOR CAP SUPPRESSOR TRANSFORMER WITH TEMP DISPLAY CRANKCASE HEATER HEATER HEATER OPTIONAL SHORT CYCLE PROTECTOR THERMAL CUT OUT T STAT SHORT CYCLE TIMER B C B R Y T STAT SET 75 F...

Page 11: ...d off Continued operation under these conditions will cause damage shorten compressor life and void the warranty A Filter Removal and Service Kooltronic Air Conditioners feature an easily removable in...

Page 12: ...ass valve fails it is strongly recommended that the Air Conditioner be returned to Kooltronic for service D Refrigerant Loss Kooltronic Air Conditioners are subjected to a series of tests to detect re...

Page 13: ...applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Blower Replace Evaporator Blower Mo...

Page 14: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Reviews: