ALARM SET

This menu affects when the built-in audio alarm will sound. There are seven options 

which are simultaneously active. Upon entering the alarm menu, the last edited line 

will flash. 

Press 

▼ or ▲ to change it. Press

 

 

to edit the value, and again to return 

to the previous menu. To disable an alarm, increase or decrease its setting to “ 

--

 ”.

    LIQ TEMP

:  Liquid Temperature (Range: 0 to 99°C)

    CH1 TEMP

:  Thermocouple #1, if attached (Range: 0 to 119°C)

    CH2 TEMP

:  Thermocouple #2, if attached (Range: 0 to 119°C)

    FAN

:  Fan Speed (Range: 100-10,000RPM)

    PUMP

:  Pump Speed (Range: 100-10,000RPM)

    FLOW

:  Coolant Flow Rate (Range: 0.1 to 20.0LPM)

       

LEVEL

:  Low Coolant Level in Reservoir (ON, or OFF to disable)

The regular audio alarm is a repeating beep.

RELAY SET

Terminals  are  provided  for  a  configurable  relay.  Wires  can  be 

connected as normally-open (NO), or normally-closed (NC), labeled 

near the terminals. 

There are seven options which are simultaneously active. Upon 

entering the relay menu, the last edited value will flash. 

Press 

▼ or ▲ to adjust 

this value. Press

 

 

to edit the value, and again to return to the previous menu. To 

disable the relay, increase or decrease its setting to “ 

--

 ”.

    LIQ TEMP

:  Liquid Temperature (Range: 0 to 99°C)

    CH1 TEMP

:  Thermocouple #1, if attached (Range: 0 to 119°C)

    CH2 TEMP

:  Thermocouple #2, if attached (Range: 0 to 119°C)

    FAN

:  Fan Speed (Range: 100-10,000RPM)

    PUMP

:  Pump Speed (Range: 100-10,000RPM)

    FLOW

:  Coolant Flow Rate (Range: 0.1 to 20.0LPM)

       

LEVEL

:  Low Coolant Level in Reservoir (ON, or OFF to disable)

PUMP SET

The pump speed can be manually set from 1 (lowest) to 10 (highest):

    PUMP(1-10)    7LV

 :  Pump Speed Level

The pump speed level will flash. 

Press 

▼ or ▲ to adjust. 

Press 

◙ 

to return to the 

previous menu.

  LIQ TEMP= 32C  

Maintain coolant coming from the system at 32°C

  CH1 TEMP= 50C  

Maintain the first thermocouple at 50°C, if attached

  CH2 TEMP= -5C  

Maintain the second thermocouple at -5°C, if attached.

 

 

 

     (This is not a sub-ambient system. Without external 

 

 

 

     assistance, this temperature may not be reached.)

  FAN PWR= 45%  

Keep fans at 45% power, regardless of temperature.

Press

 

 

again to exit configuration of the sensor. Press ◄ to return to the previous 

menu.

DISPLAY SET

The display settings configure which values you wish to appear on the front display 

and how they are shown:

    DISPLAY
    FIXED     CYCLIC

 :  Show 2 fixed values or cycle multiple values

The  first  option,  “FIXED”,  will  flash. 

Press 

◄  or  ►

 to change between these 

options. Press 

 to configure one of the selections, 

or press 

▲ to exit. 

If “FIXED” 

is selected, two lines will be shown:

    FAN SET         50%

 :  First line display option

    LIQ TEMP    30.5C

 :  Second line display option

If necessary, this cooling system will 

automatically apply heat to the liquid 

when following the user set-point. This 

can become necessary if the set-point is 

above ambient temperature and attached 

heat sources are too weak to adequately 

warm the coolant. An LED will illuminate on the front panel whenever heat is being 

applied.

CAUTION:

 To avoid permanent damage to the pump and other 

cooling system components, do not allow the liquid temperature 

to exceed 60°C (140°F) by set-point or other methods. This is the 

maximum temperature supported by the cooling system.

!

Summary of Contents for ALH-2000

Page 1: ...Superior Liquid Cooling Systems English v1 0 www koolance com ISO 9001 Printed in Korea ALH 2000 User s Manual ALH 2000 User s Manual...

Page 2: ...ation control life support or weapon launching control If these products are used in such hazardous environments Koolance Incorporated does not warrant them TRADEMARKS The Koolance name and logo are t...

Page 3: ...harmful or fatal if swallowed KEEP THIS AND ALL DANGEROUS CHEMICALS OUT OF THE REACH OF CHILDREN Please refer to the coolant MSDS available on our website www koolance com KOOLANCE CONTACT INFORMATIO...

Page 4: ...reservoir Remove the large slot headed screw with a screwdriver or large coin Coolant Filling and Powering On WARNING Most coolants are electrically conductive Use caution when filling the system and...

Page 5: ...t adjustment ALARM SET Alarm settings RELAY SET Relay Trigger settings PUMP SET Pump speed settings DISPLAY SET LED display settings When in the top menu press to enter one of the above categories To...

Page 6: ...OFF to disable PUMP SET The pump speed can be manually set from 1 lowest to 10 highest PUMP 1 10 7LV Pump Speed Level The pump speed level will flash Press or to adjust Press to return to the previous...

Page 7: ...ore doing so 2 The temperature alarm sounds and I m not sure why The offending temperature sensor and value will flash in the front display whenever an alarm sounds Check that your currently selected...

Page 8: ...age resulting from warranty service performed by a non authorized repair service No responsibility is assumed for any special incidental or consequential damages due to a defective Koolance product In...

Reviews: