ALARM SET
This menu affects when the built-in audio alarm will sound. There are seven options
which are simultaneously active. Upon entering the alarm menu, the last edited line
will flash.
Press
▼ or ▲ to change it. Press
◙
to edit the value, and again to return
to the previous menu. To disable an alarm, increase or decrease its setting to “
--
”.
LIQ TEMP
: Liquid Temperature (Range: 0 to 99°C)
CH1 TEMP
: Thermocouple #1, if attached (Range: 0 to 119°C)
CH2 TEMP
: Thermocouple #2, if attached (Range: 0 to 119°C)
FAN
: Fan Speed (Range: 100-10,000RPM)
PUMP
: Pump Speed (Range: 100-10,000RPM)
FLOW
: Coolant Flow Rate (Range: 0.1 to 20.0LPM)
LEVEL
: Low Coolant Level in Reservoir (ON, or OFF to disable)
The regular audio alarm is a repeating beep.
▲
RELAY SET
Terminals are provided for a configurable relay. Wires can be
connected as normally-open (NO), or normally-closed (NC), labeled
near the terminals.
There are seven options which are simultaneously active. Upon
entering the relay menu, the last edited value will flash.
Press
▼ or ▲ to adjust
this value. Press
◙
to edit the value, and again to return to the previous menu. To
disable the relay, increase or decrease its setting to “
--
”.
LIQ TEMP
: Liquid Temperature (Range: 0 to 99°C)
CH1 TEMP
: Thermocouple #1, if attached (Range: 0 to 119°C)
CH2 TEMP
: Thermocouple #2, if attached (Range: 0 to 119°C)
FAN
: Fan Speed (Range: 100-10,000RPM)
PUMP
: Pump Speed (Range: 100-10,000RPM)
FLOW
: Coolant Flow Rate (Range: 0.1 to 20.0LPM)
LEVEL
: Low Coolant Level in Reservoir (ON, or OFF to disable)
PUMP SET
The pump speed can be manually set from 1 (lowest) to 10 (highest):
PUMP(1-10) 7LV
: Pump Speed Level
The pump speed level will flash.
Press
▼ or ▲ to adjust.
Press
◙
to return to the
previous menu.
LIQ TEMP= 32C
Maintain coolant coming from the system at 32°C
CH1 TEMP= 50C
Maintain the first thermocouple at 50°C, if attached
CH2 TEMP= -5C
Maintain the second thermocouple at -5°C, if attached.
(This is not a sub-ambient system. Without external
assistance, this temperature may not be reached.)
FAN PWR= 45%
Keep fans at 45% power, regardless of temperature.
Press
◙
again to exit configuration of the sensor. Press ◄ to return to the previous
menu.
DISPLAY SET
The display settings configure which values you wish to appear on the front display
and how they are shown:
DISPLAY
FIXED CYCLIC
: Show 2 fixed values or cycle multiple values
The first option, “FIXED”, will flash.
Press
◄ or ►
to change between these
options. Press
◙
to configure one of the selections,
or press
▲ to exit.
If “FIXED”
is selected, two lines will be shown:
FAN SET 50%
: First line display option
LIQ TEMP 30.5C
: Second line display option
If necessary, this cooling system will
automatically apply heat to the liquid
when following the user set-point. This
can become necessary if the set-point is
above ambient temperature and attached
heat sources are too weak to adequately
warm the coolant. An LED will illuminate on the front panel whenever heat is being
applied.
CAUTION:
To avoid permanent damage to the pump and other
cooling system components, do not allow the liquid temperature
to exceed 60°C (140°F) by set-point or other methods. This is the
maximum temperature supported by the cooling system.
!
▲
▲
▲