Thermal Considerations
AM4100
Page 7 - 10
ID 36126, Rev. 2.0
P R E L I M I N A R Y
The following figure shows the thermal zones of a Full-size AM4100.
Figure 7-8: Thermal Zones of the Full-Size AM4100 Module
The following table indicates the deviation of the airflow rate on a Full-size AM4100 module.
Table 7-3:
Deviation of the Airflow Rate on a Full-Size AM4100
VOLUMETRIC
FLOW RATE [CFM]
DEVIATION OF THE AIRFLOW RATE
ZONE A
ZONE B
ZONE C
ZONE D
10
2.83%
0.43%
-1.98%
-1.29%
20
2.58%
0.29%
-1.43%
-1.43%
30
2.87%
0.57%
-1.72%
-1.72%
40
2.80%
0.50%
-1.51%
-1.79%
Note ...
The Full-size AM4100 module has an airflow rate deviation of max. ± 1.8% of
the average value of the four thermal zones (max. ± 25% is allowed).
Positive deviation means increased airflow.
Negative deviation means decreased airflow.
Note ...
The Full-size AM4100 module provides an open area of 56%. According to the
PICMG AMC.0 Specification, an open area of 20 to 70% perpendicular to the
airflow path is recommended.
open area
I/O Zone
32.8
Zone A
34
Zone B
34
Zone C
34
Zone D
34