32
distance between portable and mobile RF communications equipment
(transmitters) and the concentrator as recommended below, according to
the maximum output power of the communications equipment.
Output power
of transmitter
in Watt (W)
Separation distance according to frequency of
transmitter(m)
150kHz - 80MHz
d
=
1.2
P
80MHz - 800MHz
d
=
1.2
P
800MHz - 2.5GHz
d
=
2.3
P
0.01
0.12
0.12
0.23
0.1
0.38
0.38
0.73
1
1.2
1.2
2.3
10
3.8
3.8
7.3
100
12
12
23
For transmitters rated at a maximum output power not listed above, the
recommended separation distance “d” in meters (m) can be estimated
using the equation applicable to the frequency of the transmitter, where P
is the maximum output power rating of the transmitter in watts (W)
according to the transmitter manufacturer.
Note 1: From 80MHz to 800MHz, the higher frequency range applies.
Note 2: These guidelines may not apply in all situations. Electromagnetic
propagation is affected by absorption and reflection from structures, objects
and people.