background image

18

OIL LEVEL

INDICATOR

VOLTS/FREQUENCY

WORKING/TOTAL HOURS

DC 12V  8.3A

FUSE

DC BREAKER

10A

ATS

OUTPUT

230V 63A

230V 32A

230V 16A

OVERLOAD

AC 16A

230V 16A

ON

OFF

230V

CIRCUIT BREAKER

STARTER SWITCH

HEAT

OFF

ON

ENGINE START

Fig. 10

Control panel for model  KS 14-1DE ATSR

Contact strip for models:
KS 13-2DEW ATSR , KS 13-2DEW 1/3 ATSR
KS 14-2DE ATSR, KS 14-2DE 1/3 ATSR

3

5

10

9

7

12

1. Start switch

2. Oil level indicator

3. LED-display

4. Circuit breakers for 16 A outlets

5. Circuit breaker

6. 230 V 2*16 А outlet

7. 230 V 1*32 А outlet

8. 230 V 1*63 А outlet

9. ATS input (universal 5-pin)

10. Grounding connector
11. 12V/8А DC terminals
12. Fuse for 12 V connector

1

2

8

11

4

6

230V

Grounding

1. L - Phase
2. N - Neutral

Summary of Contents for HEAVY DUTY KS 11-2DE ATSR

Page 1: ...d this manual carefully before use Owner s Manual DIESELGENERATOR KS 9200HDE ATSR KS 11 2DE ATSR KS 13 1DEW 1 3 ATSR KS 13 2 DEW ATSR KS 13 2 DEW 1 3 ATSR KS 14 1 DE ATSR KS 14 2 DE ATSR KS 14 2 DE 1...

Page 2: ...ultifunction Control Unit ___________________ 20 12 Getting Started _ _ _ _ _ _________________ 25 13 Maintenance ________________ ________ 29 14 Maintenance Schedule _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _...

Page 3: ...to make changes in the product design configuration and construction The images and drawings in this manual are for reference only and may differ from the actual components and inscriptions on the pro...

Page 4: ...this increases the risk of electric shock Avoid direct contact with grounded surfaces pipes radiators etc Be careful when working with the power cord Replace it immediately in case of damage as damage...

Page 5: ...it is placed on a flat level surface and the engine switch is in the OFF position Check the connection of moving parts inspect for damaged parts that affect the operation of the generator Eliminate da...

Page 6: ...ator with wet or dirty hands h Observefiresafetyregulations donotoperate the generator near open flame i Do not touch The generator dampener becomes hot during operation a b c f e d a Wear protective...

Page 7: ...Reinforced frame 2 Fuel tank 3 Damper 4 Anti vibration mounts 5 Fuel filter 6 Oil filter 7 Oil dipstick 8 Oil drain valve 9 Control panel 10 Soundproofanti vandalhousing 11 Transport kit 3 9 Model KS...

Page 8: ...nce only and may differ from actual components and inscriptions on the products 11 Model KS 13 2DEW ATSR KS 13 2DEW 1 3ATSR KS 14 2DE ATSR KS 14 2DE 1 3ATSR 1 Fuel tank 2 Soundproofanti vandalhousing...

Page 9: ...orrespond to the number power and voltage of the generator outlets 2 x start keys Top cover key Fuel filter Fuses 10 12 mm open end wrench 4 17 mm open end wrench 13 16 mm open end wrench Set of screw...

Page 10: ...r key Door keys Set of screws Wheels 4 pcs Formodels KS13 1DEW1 3ATSR KS13 2DEWATSR KS13 2DEW1 3ATSR Oil filter key Air filter Fuel filter Oil filter 2x start keys Door keys Portable plugs plugs corre...

Page 11: ...12 8 3 12 8 3 Engine model KS 540HD KS 690HD Engine type diesel powered one cylinder four stroke air cooled Engine power HP 14 15 Crankcase volume cm3 1 65 2 2 Engine olume cm3 531 668 Power output co...

Page 12: ...ncy voltage SmartGen multifunction digital control unit Noise level Lpa Lwa dB 73 98 69 94 69 94 Output 12V A Engine model KS 820HD KS 820HD KS 820HD Engine type diesel powered two cylinder four strok...

Page 13: ...tGen multifunction digital control unit Noise level Lpa Lwa dB 74 99 70 95 70 95 Output 12V A Engine model KS 1020HD KS 1020HD KS 1020HD Engine type diesel powered two cylinder four stroke air cooled...

Page 14: ...to the generator active and reactive Active power consumers include all power consumers whose power input is converted into heat heaters Reactive power consumers include all power consumers equipped...

Page 15: ...Do not start the engine until it is filled with sufficient amount of motor oil Recommended motor oil SAE 10W30 SAE 10W40 Recommended motor oil grade API Service SG type or higher Motor oil quantity se...

Page 16: ...r for 16 A outlets 12 230V 1 16 outlet 13 Air heater Fig 6 Control panel for model KS 9200HDE ATSR Control panel for model KS 11 2DE ATSR 3 4 1 2 12 11 3 5 6 13 5 9 10 8 Fig 7 7 11 10 9 7 6 12 1 Start...

Page 17: ...utput 10 Grounding connector 11 12V 8 DC terminals 12 Fuse for 12V connector 13 Engine overtemperature indicator 14 Oil level indicator 230V 32A DC 12V 8 3A OIL LEVEL INDICATOR STARTER SWITCH VOLTS FR...

Page 18: ...connector 3 Start switch 4 Circuit breakers 5 VTS system single three phase switch position 1 230V position 0 OFF disabled 6 230V 1 63 outlet 7 400V 1 16 outlet 8 400V 1 32 outlet 9 230V 1 32 outlet 1...

Page 19: ...or model KS 14 1DE ATSR Contact strip for models KS 13 2DEW ATSR KS 13 2DEW 1 3 ATSR KS 14 2DE ATSR KS 14 2DE 1 3 ATSR 3 5 10 9 7 12 1 Start switch 2 Oil level indicator 3 LED display 4 Circuit breake...

Page 20: ...CONTROL DEVICE N 230V ATS OUTPUT ON OFF 230V CIRCUIT BREAKER 230V 32A 230V 16A 400V 16A 400V 32A L ON OFF 230V 400V CIRCUIT BREAKER AC400V AC AC230V STARTER SWITCH HEAT OFF ON ENGINE START 1 3 2 4 5...

Page 21: ...nspection 11 SMARTGEN MULTIFUNCTION CONTROL UNIT The SMART GEN HGM501 multifunction control unit is a smart digital controller that combines digital and intelligent functions to monitor and protect th...

Page 22: ...urrent frequency battery voltage total operating hours maximum 999 hours engine temperature for models KS 13 2DEW ATSR KS 13 2DEW 1 3 ATSR 3 Controller protects the engine from over and undervoltage u...

Page 23: ...tion press this button to switch to the upper LED DOWN SCROLL 1 When setting the parameters pressing this button decreases the set value 2 During normal operation press this button to switch to the bo...

Page 24: ...ltage power and frequency displays will show the actual readings Press the or button to switch between indicators 1 6 and the multifunction display will show the corresponding settings Press the butto...

Page 25: ...riggered After that the frequency LED continues to flash and shows the previous alarm OVERLOAD PROTECTION If the set value is exceeded by 5 or less the alarm will not be triggered If the set value is...

Page 26: ...han 16 5 V the gas discharge display or the LED display will start to flash but no safety shutdown will be triggered 12 GETTING STARTED Before starting the engine make sure that the power rating of po...

Page 27: ...r position ON If the engine does not start after three or four attempts air might have penetrated the fuel system Remove air from the fuel system drain diesel fuel together with excess air Before conn...

Page 28: ...ptheengine proceedasfollows 1 Disconnectallthedevicesconnectedtothegenerator setthecircuitbreakertoOFF 2 _Allowthegeneratortooperateatidlefor3minutesforthealternatortocooldown 3 _SetthestartkeytoOFF 4...

Page 29: ...umers three phase generators Mode switching is allowed only when no power consumers are connected USINGASATHREE PHASEGENERATOR The three phase diesel generator should have the power distributed to all...

Page 30: ...e damage and other effects of improper storage of equipment _Damage caused by maintenance work performed by unskilled technicians Observe the instructions in this manual The generator must be maintain...

Page 31: ...k motor oil Check coolant level Check fan belt Check fuel drain residues and impurities Check for leaks Check assembly of mounting elements Check exhaust color Check meters and water cooling indicator...

Page 32: ...il level drops fresh oil must be added to ensure proper operation of the generator Check the oil level according to the maintenance schedule To drain oil proceed as follows 1 Place an oil drain tray u...

Page 33: ...maintenance of the air filter is necessary to maintain sufficient air flow in the carburetor The maintenance intervals should be shorter when operating the generator in dusty environments Fig 15 Donot...

Page 34: ...ueltank Fuel filter in the fuel line Thisfiltermustbechangedevery250operatinghours Itislocatedunderthefuel tankonthefuelhosethroughwhichfuelenterstheenginefromthetank Toreplaceit 1 Loosen the metal br...

Page 35: ...bestoredinadry well ventilatedareathatisfreefromdust Keep away from children Thegeneratormustalwaysbereadyforuse Anymalfunctionsinthe generatormustberepairedbeforeplacingthegeneratorinstorage Please n...

Page 36: ...ilter Engine starts but no output voltage Circuit breaker tripped SetthecircuitbreakertoON Connectioncablesofpoor quality Checkcablesfornormal operation replace ifextension cableisused Faultyconnected...

Page 37: ...release Check oil pressure sensor and wiring Emergency shutdown during operation Check the appropriate switch and wiring according to the information on the display Unable to start Check fuel return...

Page 38: ...1000 Grill 50 250 Oven 1200 2300 Fridge 1000 2000 TV set 100 150 Perforator 100 400 Drill 600 1400 Freezer 400 800 Grinder 100 400 Circular saw 300 1100 Crank gear 750 1600 Jigsaw 650 2200 Planer 250...

Page 39: ...eclaimedmalfunctioncannotbediagnosedordemonstrated If proper operation of the product can be restored following cleaning from dust and dirt appropriate adjustment maintenance oilchange etc Iftheproduc...

Page 40: ......

Page 41: ...www ks power de info dimaxgroup de CONTACTS Polska DIMAX International Poland Sp z o o Polen Warczawska 306B 05 082 Stare Babice www ks power pl info pl dimaxgroup de 47 02222 www ks power com ua sal...

Reviews: