Installation requirements
Topics
Supply voltage requirements, page 37
Uninterruptible power supply (UPS) requirements, page 37
Cables and wiring requirements, page 38
Compass deviation requirements, page 38
Dry docking requirements, page 39
Requirement for classification approval, page 39
Supply voltage requirements
As a general rule, the supply voltage must kept within ±10% of the installation’s nominal
voltage.
The EK80 software supports several different transceiver units. The supply voltage must
be kept within the specific requirement for each transceiver in the EK80 system. For
detailed requirements, see the relevant data sheets and end user documentation.
Maximum transient voltage variations on the main switchboard’s bus-bars must not
exceed -15% to +20% of the nominal voltage (except under fault conditions).
Related topics
Installation requirements, page 37
Simrad EK80, page 13
Uninterruptible power supply (UPS) requirements
We recommend that the EK80 system is powered using an Uninterruptible Power Supply
(UPS) with sine wave output.
The Uninterruptible Power Supply (UPS) must have the capacity to independently
maintain power to the EK80 for a minimum of 10 minutes. This ensures that the EK80
can be turned off in a controlled manner in the event of a power failure.
Related topics
Installation requirements, page 37
Simrad EK80, page 13
Uninterruptible power supply (UPS), page 35
Summary of Contents for Simrad EK80
Page 1: ...kongsberg com simrad Simrad EK80 INSTALLATION MANUAL ...
Page 2: ......
Page 12: ...10 394149 D Simrad EK80 ...
Page 313: ...394149 D 311 Drawing file ...
Page 314: ...312 394149 D Simrad EK80 Installation Manual ...
Page 317: ...394149 D 315 Drawing file ...
Page 318: ...316 394149 D Simrad EK80 Installation Manual ...
Page 320: ...318 394149 D 201575 Transducer connector assembly and wiring Simrad EK80 Installation Manual ...
Page 352: ... 2020 Kongsberg Maritime ISBN 978 82 8066 182 1 ...
Page 353: ......
Page 354: ...Installation Manual Simrad EK80 ...