6. ELECTRICAL INSTALLATION
Only qualified professionals may perform electrical installation works in accordance with the manufacturer’s instructions
and applicable legal acts and safety requirements. Before installation of any electrical components:
•
Make sure the unit is unplugged from the mains.
•
If the unit has been standing in an unheated room for a long time, make sure there is no con-
densation inside and check if contacts and electronic parts of the connectors are not damaged
by moisture.
•
Inspect the power cable ant other wiring for damage in insulation.
•
Locate the wiring diagram for your unit according to the unit type.
6.1. Requirements for Electrical Connection
•
Connect the unit only to a proper power outlet with protective earthing. Earthing must be in-
stalled according to the EN61557, BS 7671 requirements.
•
It is recommended to connect AHU to the mains via automatic circuit breaker with 300 mA cur-
rent leakage protection (type B or B+).
•
Control cables should be installed at least 20 cm away from power cables to reduce the possibil-
ity of electrical interference.
•
All external electrical elements must be connected strictly according to the wiring diagram of
the unit.
•
Do not disconnect the connectors by pulling wires or cables.
Lead-in cable diameter depends on a maximum current specified in the technical data print-out of the specific unit.
Current, A
Cable type
15
5 × 1,5 mm
2
(Cu)
21
5 × 2,5 mm
2
(Cu)
27
5 × 4,0 mm
2
(Cu)
34
5 × 6,0 mm
2
(Cu)
50
5 × 10,0 mm
2
(Cu)
70
5 × 16,0 mm
2
(Cu)
85
5 × 25,0 mm
2
(Cu)
6.2. Connection of Electrical Components
All internal and external elements of the unit are connected to the main board of the C5 control panel (marked as “RG1” in
wiring diagrams), located inside the unit. In some units, you will need to unscrew the metal cover to access the control panel.
You can see the exact location of the C5 control panel in the unit in section “Unit components”.
37
38
39
40
41
42
43
44
45
46
47
48
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
1
2
3
4
5
6
7
8
9 10
11
12
25
26
27
28
29
30
1
2
2
3
4
1
Fig. 17.
C5 controller main board
1 – control panel connection, 2 – Intranet or Internet connection, 3 – inner connections of components,
4 – terminals for external components