SIA KOMFOVENT reserves the right to make changes without prior notice
Fire damper UVA60 H / UVA120 H installation manual 21-01
21
5.
PERIODICAL INSPECTIONS
It is a mandatory requirement of EN 15650 standard that all fire dampers must be checked at least twice a year.
Below is
Komfovent recommended maintenance inspection checklist.
Year of inspection
Year 1
Year 2
Year 3
Year 4
Year 5
Date of inspection
01.01.21
Inspected by
Installation date:
Checked by / date:
RECORDS OF THE FIRE DAMPER
Accepted by / date:
PERIODICAL INSPECTIONS
Fire damper ref. No.
FD 25
Location
Server room 121
Damper type and size
UVA120H-200
Mounted in wall (w) or slab (s) thickness
W100
Access to the damper compliant
Yes
Installation in acc. to manufacturer’s instructions
Yes
Correct operation of the fire damper
Yes
Damper cleanness (accumulated dust, grease)
No
Lubricate all moving Parts (done/not done)
Yes
Damper condition (corrosion, rust)
No
Fusible link or thermosensor was replaced
No
Damages or modifications
No
Blade and sealing material are undamaged
Yes
Wiring of the end switches is undamaged and connected
Yes
Wiring of the actuator is undamaged and connected
NA
Pass / fail blade drop test
Pass
End switches indicate blade closing
Yes
Fire damper left in OPEN position
Yes
Year of inspection
1
x
2
3
4
5
Comments
Summary of Contents for UVA120 H
Page 1: ...2021 ...