7.5.2. Functions
In this menu item, the user can activate and set
additional unit functions.
blank box: function is not activated
gray box: function is activated, but currently not operat-
ing
blue box: currently operating function
7.5.2.1. Air quality control
Air quality control is designed according to:
•
CO
2
sensor
1
[0...2000 ppm];
•
air quality sensor VOCq [0...100 %];
•
air pollution sensor VOCp [0...100 %];
•
relative humidity sensor [0...100 %];
•
temperature sensor [0...50 ºC].
Depending on the type of the selected sensor, the value of the air quality
function to be maintained is set, and the air handling unit intensity will be ad-
justed according to that value. Ventilation intensity will be increased automati-
cally in the case of deviation from the set value and decreased again when it
is approached. For example, if the unit is designed with the CO
2
maintenance
function and is equipped with a CO
2
sensor, after setting value 800 ppm, this
set CO
2
level will be maintained by adjusting ventilation intensity, i.e. ventilation intensity will be in-
creased if the CO
2
level grows and will be decreased when it returns to the previous condition.
The function of air quality operates only if no other below function is active at the
same time:
• summer night cooling;
• min. temperature control;
• outdoor compensated ventilation.
7.5.2.2. Operation on demand
The air handling unit start-up function is designed to start the unit which
currently off, when one of the selected parameters has exceeded the critical
limit.
The function provided for the start-up of the unit according to:
•
room CO
2
sensor;
•
room air quality sensor VOCq;
•
room air pollution sensor VOCp;
•
room relative humidity sensor;
•
room temperature sensor.
Operation on demand (start-up / shut-down) is performed by the same sensor
which is used in the control of the “Air quality function”.
A room sensor with the analogue output (0...10 V DC) should be designed for this
function.
1
Factory setting.
Functions
1 / 2
Air quality
control
Operation on
demand
Outdoor compen
-
sated ventilation
Summer night
cooling
Minimum tempera-
ture control
Functions
Settings
Overview
Scheduling
Menu
Reset settings
Enable
Setpoint 1
1000 ppm
Setpoint 2
880 ppm
Mode 1
COMFORT 1
Mode 2
COMFORT 2
Air quality control
Reset settings
Enable
Setpoint
1000 ppm
Operation on demand