4.3. Ductwork

The air flows in/out air handling unit through ductwork. We recommend using galvanized steel (Zn 275 gr/m

2

ductwork, to ensure easy cleaning and durability. It is necessary to use the ductwork system with low air flow 

rate and small pressure drop to have necessary air volume and low sound level and save the energy. The 

appropriate sound attenuators will reduce the noise level of the fans in the premises. All ductwork should be 

insulated with 50–100 mm thickness insulation to avoid the condensation.

Note: 

temperature sensor B1 has to be mounted in the supply air duct under electric heater (see the func-

tional diagram in Control System Electrical Installation and Operation Manual). It is necessary to leave space 

in straight air duct for sensor mounting and guarantee the space for maintenance and service work. Minimal 

space between the unit and B1 sensor is the space of double air duct diameter.

Ductwork, steelwork and any other services should not be supported 

off the unit.

It is recommended to install air dampers in the inlet and outlet ducts. For 

ventilation units with water air heater, it is mandatory to use inlet air closing 

damper with spring return mechanism.

4.4. Final Inspection

After installation of the unit, a thorough inspection should be carried out. This should include inspecting 

the inside of the unit and removing debris and tools, which may have been left behind by on site contractors. 

Replace any panels, which may have been removed and close all access doors, ensuring that the door sealing 

gaskets have not been damaged.

5. MAINTENANCE

It is recommended to carry out routine maintenance of the air handling unit 3–4 times per year. With units 

mounted on ceilin do not release the door to the key to open the door. Do not release the door to swing freely, 

but open it slowly at a 90 degree angle. Be careful while opening, because clogged filters might fall out.

Besides preventive maintenance inspection, the following operations should be performed:

1.  Rotary heat exchanger check. 

Inspection of the rotary heat exchanger is performed once per year. Free 

rotation of the rotary heat exchanger, continuity of the rotating belt, absence of damages of the rotor drums 

and the seal gasket are checked. It is necessary to check the stretch of belt. Free belt will slide and the 

 

efficiency of rotary heat exchanger will fall down. To reach maximal efficiency, rotor must turn at least 8 

times per minute. Polluted heat exchanger will decrease efficiency. Clean heat exchanger with an air blast 

or wash with tepid water. Check out water falling on the electric motor. 

2.

 

Plate heat exchanger check. 

Inspection and dedusting of the plate heat exchanger is performed once per 

year (it is removed from the unit and blown with an air blast or washed with tepid water).

 

Plate heat exchanger cleaning.

 If plate heat exchanger cleaning by compressed air is not effective, it can 

be washed with soapsuds, or if needed – use degreasing soak for metal (aluminum) cleaning. Leave plate 

heat exchanger to dry in a warm place. It can be mounted only when it is absolutely dry.

Note: 

plate heat exchanger may be replaced with summer cassette (for units without by pass), when re-

cuperation is needless.

3.  Fans check (once per year). 

Polluted fans decrease efficiency. 

Before performing any inspection work, check whether the unit is 

switched off from the electric power supply.

 

 

Fans should be carefully cleaned with textile or soft brush. Do not use water. Do not break balance. Check 

if direction of fan turns is right, because wrong direction of turns gives only 30 % rating. Check if fan freely 

rotates and is not mechanically damaged, if impeller does not touch suction nozzles, fan does not spread 

noise, the pressure tubes are connected to the nozzle (if it is required), mounting bolts are screwed.

 

The rubber couplings connecting the motor base and the unit should be visually inspected for signs of wear 

and replaced as necessary.

 

Any unusual noise or vibration when the fan is running should be immediately investigated, as this usually 

an indication of wear or imbalance in the fan system.

4.  Air heater check. 

Recommended to perform periodical inspection and cleaning of heater. Check the 

plates of water air heater. The air heater is cleaned with hoover from supply air side or with air blast from 

exhaust air side. If it is very dirty, wash with tepid water, which will not make corrosion of aluminium. Check 

if position of return water temperature sensor is right. Check if electric air heater is properly fixed, wires 

Summary of Contents for Domekt CF 250 F

Page 1: ...DOMEKT EN Installation and service Manual ...

Page 2: ......

Page 3: ...lly associated with EEE At the same time your cooperation in the correct disposal of this product will contribute to the effective usage of natural resources For more information about where you can drop off your waste equipment for recycling please contact your local city office waste authority approved WEEE scheme or your household waste disposal service Content 1 SAFETY REQUIREMENTS 4 2 TRANSPO...

Page 4: ...ing the unit check correct position of air filters Service maintenance should be carried out only in conformity with the instructions specified herein below If main cable is damaged only manufacturer service team or trained technician must change it in order to avoid accidents Drilling and using self tapping screws on the unit casing is prohibited where it is not provided by the construction since...

Page 5: ... ambient temperature and relative humidity The unit is intended to be installed in the domestic or non residential premises Mineral wool is used for thermal insulation and sound attenuation Units cover panels are 25 50 mm thick As standard the unit is designed for indoor placement In cold wet rooms possible icing or condensation on the housing inside and outside The operating temperature range for...

Page 6: ...nger as it is not freez ing even at the temperatures of 30 C if the humidity level of the air is appropriate In the units with counter flow or cross flow plate exchangers without inte grated preheater it is necessary to install additional duct mounted pre heater in the outside air intake duct which will ensure temperature of the intake air higher than 4 C Selecting the management without pre heate...

Page 7: ... 2 Preheater should be installed to increase the supply air temperature It is recommended to keep air handling unit constantly running and in cases when ventilation is not necessary switch it to the minimum inten sity 20 In that way good indoor climate will be maintained and con densation inside of the unit will decrease avoiding humidity damage to electronic components Example No 1 Temperature of...

Page 8: ...ce D_20 07 8 Air Handling Units Schemes 6 3 4 5 7 1 2 DOMEKT R 400 V DOMEKT R 450 V 5 2 7 4 3 6 1 B A C E D E DOMEKT R 190V 200V 6 3 1 5 4 C B A E D DOMEKT R 300 V D A C B 3 4 1 5 6 DOMEKT R 400 H E D A C B 3 4 1 5 6 2 DOMEKT R 250 F C6 C B A D E 6 3 1 5 4 2 DOMEKT R 400 F ...

Page 9: ...erve the right to make changes without prior notice D_20 07 9 E D A C B 6 3 1 5 4 2 DOMEKT R 700 H D A E C B 6 3 1 4 5 2 DOMEKT R 600 H B E A D C 2 5 4 3 6 1 DOMEKT R 500 V DOMEKT R 700 V C B D A 2 6 1 3 5 4 DOMEKT R 700 F ...

Page 10: ...ve the right to make changes without prior notice D_20 07 10 A D C B 3 6 2 1 DOMEKT CF 400 V C D 4 3 1 5 6 8 B E A 2 7 B C E D A DOMEKT PP 300 V 450 V 6 3 1 7 5 4 8 D A B C DOMEKT CF 250 V D A B C 1 2 6 3 5 4 2 DOMEKT CF 250 F ...

Page 11: ... C B 6 2 3 4 5 2 DOMEKT CF 700 V 3 5 2 A B DOMEKT S 650 F 800 F 1000 F A Outdoor intake B Supply air C Extract indoor D Exhaust air E E Kitchen hood connection by pass extraction without heat recovery 1 Rotary or plate heat exchanger 2 Electric or water air heater 3 Supply air filter 4 Exhaust air filter 5 Supply fan 6 Exhaust fan 7 Air by pass damper 8 Condensate drain the water trap must be inst...

Page 12: ...g The place for the unit must be selected with allowance for minimum access to the unit for maintenance or service and must comply with safety requirements Opening for inspection can not be smaller than dimensions of the unit and unit itself must be mounted in a way that if needed for example in case of complicated repair it can be easily dismounted Minimum Maintenance Space for Horizontal Units 1...

Page 13: ...eserve the right to make changes without prior notice D_20 07 13 B ceiling A min 100 mm 5 B 1 Inspec tion trapdoor 2 2 3 5 a Picture 2 2 1 3 5 A A D C B B 5 b Picture Only F type units Only R 250F R 400 F and 700 F units ...

Page 14: ...right to make changes without prior notice D_20 07 14 DOMEKT R 400 V Unit brackets positions B A 641 604 57 662 30 300 600 30 Ø125 Ø160 6 Picture DOMEKT R 450 V Unit brackets positions Ø125 Ø160 A 57 667 704 B 30 340 30 680 7 Picture ...

Page 15: ...notice D_20 07 15 DOMEKT CF 250 V Unit brackets positions view 1 35 260 520 590 595 20 B A 510 700 824 795 8 Picture DOMEKT CF 250F CF 500F CF 700F Units brackets positions 15 9 Picture DOMEKT CF 400 V Unit brackets positions 520 750 838 867 598 600 260 39 10 Picture ...

Page 16: ...ed with heating cable A condensate pipe and a drain trap Drain scheme of Vertical Unit view 1 D 15 12 a Picture Drain scheme of Horizontal Unit view 2 D 15 view 2 12 b Picture The bend of the water trap can be repositioned by turning it to the right or the left The drain line from the water trap must be arranged so that it will not damage adjacent unit sections or building elements If the drain li...

Page 17: ...r complete condensate drainage from the air handling unit and prevention of penetration of offensive odours from an effluent into the ventilation system In case of the outdoor operation of the air handling unit the siphon and the bleeders should be heated with an electric thermal cable if ambient air temperature tamb 0 C The siphon and the bleeders should be heat insulated with an insulating mater...

Page 18: ...SUP SUP Supply air duct connection DOMEKT R 190V 200V Unit hanging scheme without kitchen hood 1 2 3 4 5 8 9 8 5 6 7 SUP SUP 1 Air handling unit DOMEKT R 190V 200V 2 Wall plug 8 50 screw 4 5 50 3 Wall mounting bracket 4 Self tapping screw 4 2 13 5 Unit bracket 6 Bottom bracket 7 Screw M4x16 DIN 7895 8 Bracket for decorative panel 9 Screw 2 5 16 with cone head ...

Page 19: ... 1 Air handling unit DOMEKT R 190V 200V 2 Kitchen hood adapter 392 12 3 Kitchen hood 392 12 4 Standard kitchen hood 5 Wall plug 8 50 screw 4 5 50 6 Wall mounting bracket 7 Unit bracket 8 Self tapping screw 4 2 13 9 Bracket for decorative panel 10 Screw 2 5 16 with cone head Dimensions for mounting furniture panel 22 625 600 500 250 22 32 5 500 250 32 5 Ø 2 d e p t h 5 m m 1 6 h o l e s 13 Picture ...

Page 20: ...ling kitchen hood bottom cover plate must be removed by remooving fixing screws 14a pic 14b Picture Installation of standard kitchen hood 14c Picture Installation of kitchen hood 392 12 1 Kitchen hood adapter 392 12 2 Standard kitchen hood 3 Kitchen hood 392 12 4 Screws M4 for hood fixation 4 picture 5 Self tapping screws 4 2 13 for adapter fixation 10 picture 5 10 4 4 4 4 3 2 1 ...

Page 21: ...prior notice D_20 07 21 Dimensions for the DOMEKT R 190V 200V installation space 804 42 325 625 777 500 140 140 4 560 575 600 15 Picture Dimensions with standard kitchen hood 16 Picture Dimensions with kitchen hood 392 12 325 42 738 94 625 140 4 560 140 25 600 ...

Page 22: ..._20 07 22 DOMEKT PP 300 V DOMEKT PP 450 V Unit brackets positions 7 view 1 2 3 5 6 9 4 2 8 7 35 330 35 730 740 765 790 653 6 B A 17 Picture 1 Screw 2 Wall plug 3 Hanging bracket 1 4 Hanging bracket 2 5 Bolt M5 6 Gasket 7 Self tapping screw 8 L shape bracket 9 Washer M5 DIN9021 ...

Page 23: ...C 4 8 3 2 1 1 2 6 5 7 C 18 Picture When closing unit doors fixing nuts 7 should be easily tightened by hand Do not over tighten since it will damage the doors or casing of the unit 1 Wall plug 8 50 2 Screw 4 5 50 3 Upper bracket 4 Fixing bolt M5 30 5 Self tapping screw 4 2 13 6 Lower bracket 7 Door fixing nut 8 Self tapping screw 4 2 13 optional ...

Page 24: ...cling centre or the like Glycol is highly dangerous to consume and can cause fatal poisoning or damage the kidneys Contact a doctor Avoid breathing glycol vapour in confined spaces If you get glycol in your eyes fush them thoroughly with water for about 5 minutes When operating air handling unit in the temperatures lower than 0 C it is necessary to use glycol additionally or assure the reversible ...

Page 25: ...ry heat exchanger continuity of the rotating belt absence of damages of the rotor drums and the seal gasket are checked It is necessary to check the stretch of belt Free belt will slide and the efficiency of rotary heat exchanger will fall down To reach maximal efficiency rotor must turn at least 8 times per minute Polluted heat exchanger will decrease efficiency Clean heat exchanger with an air b...

Page 26: ...heck Change air filters when air filter clogging is indicated We recommend changing filters at least twice per year before and after heating season or more1 Filters are one time used We do not recommend cleaning them Stop the air handling unit before changing filters Pressure sensor 20 Picture 7 Pressure sensor setting which indicates impurity of filters Pressure sensor is set according to EN 1377...

Page 27: ...1 6 2 0 2 180 4 250 1 125 700 F 424 1272 1240 854 80 1 230 11 6 2 0 2 176 4 250 DOMEKT P 300 V 345 740 725 700 42 1 230 5 5 1 0 2 67 5 125 450 V 345 740 725 700 42 1 230 6 7 1 0 2 167 5 125 DOMEKT CF C6 250 F 294 1282 1250 604 43 1 230 8 3 1 5 2 89 4x160 400V 600 600 765 750 55 1 230 10 5 2 0 2 91 4x160 500F 295 1430 1400 1045 70 1 230 11 6 2 0 2 171 4x200 700H 497 1533 1500 700 95 1 230 12 0 2 0 ...

Page 28: ...0 F 145 145 145 145 165 225 165 225 400 H 267 157 267 157 183 153 153 183 450 V 130 255 130 255 110 0 0 110 700 H 402 257 257 402 198 198 198 198 500 V 700 V 229 186 229 186 190 228 228 190 600 H 375 285 375 285 170 120 170 120 700 F 202 202 202 202 202 218 202 218 DOMEKT P 300V 100 140 100 140 85 180 185 110 450 V 100 140 100 140 85 180 185 110 DOMEKT CF C6 250 F 128 128 128 128 162 192 162 142 4...

Page 29: ...260 46 46 600 H KF5 KF7 475 235 46 46 700 V H KF5 KF7 540 260 46 46 700 F KF5 KF7 370 360 46 46 DOMEKT P 300 V KF5 KF7 300 200 46 46 450 V KF5 KF7 300 200 46 46 DOMEKT CF 250 F KF5 KF7 265 250 46 46 400 V KF5 KF7 235 350 46 46 500 F KF5 KF7 484 250 46 46 700 V H KF5 KF7 390 300 46 46 700 F KF5 KF7 400 300 46 46 DOMEKT S 650 F KF5 KF7 235 371 46 800 F KF5 KF7 287 371 46 1000 F KF5 KF7 558 287 46 Su...

Page 30: ......

Page 31: ......

Page 32: ... iela 1 LV 1004 Riga Tel 371 24 664433 info komfovent lv www komfovent lv www komfovent com PARTNERS AT J PICHLER Gesellschaft m b H www pichlerluft at BE Ventilair group www ventilairgroup com ACB Airconditioning www acbairco be CZ REKUVENT s r o www rekuvent cz CH WESCO AG www wesco ch SUDCLIMATAIR SA www sudclimatair ch CLIMAIR GmbH www climair ch CH LI Trivent AG www trivent com DK Øland A S w...

Reviews: