EB-20X Installation & Service Manual |
Motor Data Package
Kollmorgen | kdn.kollmorgen.com | September 2020
35
3. 6 TYPICAL CURRENT AND VOLTAGE (WAVE FORMS AT MOTOR)
3.6.1. CURRENT PHASE C
CSW1
200 V
V = -8.0 V
5 ms
VZR -0.16
T = 19.65 ms
3.6.2. VOLTAGE LINE A-C
CSW1
200 V
V = -8.0 V
5 ms
VZR -0.16
T = 19.65 ms
200 V
5 ms
DSW1
TPOS-7
The EB-206-C is illustrated at 1500 rpm, 4.4 lb-ft.
3. 7 INTERMITTENT DUTY OPERATION
If a motor operates intermittently, it is not necessary that the peak load torques fall within the
motor’s continuous torque capabilities. However, it is important that the RMS (root mean square)
load torque be inside the continuous duty zone. The key here is that a sufficient OFF time follows
each ON time of the motor.
(EQ1) gives the RMS torque:
T
RMS
=
T
1
t
1
+ T
2
t
2
+ . . . T
i
t
i
2
2
2
t
1
+ t
2
+ . . . t
i
(EQ-1)
T
i
= Torque at Time i
t
i
= Duration of time i