Section 2 Installation
2.5.3
Neutral Connection
Connect the neutral from the main panel to the neutral
lug in the ATS enclosure.
Ground the system according to NEC and local codes.
2.5.4
Neutral Bonding Jumper, Service
Entrance Models
The
transfer
switch
is
shipped
with
the
neutral-to-ground jumper installed.
For non-service
entrance applications, disconnect the neutral-to-ground
bonding jumper.
See the transfer switch dimension
drawing.
2.5.5
Engine Start Function
The engine start function is controlled by the RDC2/DC2
controller on the generator set. There are no engine
start terminals on the Model RXT ATS.
Cable Sizes
AL/CU UL-Listed Solderless Screw-Type Terminals for External Power Connections
Switch
Size,
Amps
Range of Wire Sizes, Cu/Al
Switch
Phases
Normal and Emergency
Load
Neutral
Ground
100
Standard
1
(1) #14 -- 1/0 AWG
(1) #14 – 1/0 AWG
(3) #12 – 1/0 AWG
(9) #4 – 14 AWG
With load
center
1
(1) #14 – 1/0 AWG
per customer-supplied
circuit breaker
(1) #2 – 2/0 AWG
(9) #4 – 14 AWG
Service
Entrance
1
Normal: (1) #12 – 2/0
AWG
Emerg: (1) #6 – 250
MCM
(1) #6 – 250 MCM
(3) #6 – 250 MCM
(3) #14 – 1/0 AWG
3-Phase
3
(1) #8 – 3/0 AWG
(1) #8 – 3/0 AWG
(3) #6 AWG – 3/0 AWG
(3) #6 – 3/0 AWG
200
Standard
1
(1) #6 AWG – 250 MCM
(1) #6 AWG – 250 MCM
(3) #6 AWG – 250 MCM
(9) #4 – 14 AWG
Service
Entrance
1
Normal: (1) #4 – 300
MCM
Emerg: (1) #6 -- 250
MCM
(1) #6 AWG – 250 MCM
(3) #6 AWG – 250 MCM
(3) #14 – 1/0 AWG
3-Phase
3
(1) #6 AWG – 250 MCM
(1) #6 AWG – 250 MCM
(3) #4 AWG – 600 MCM
(6) 1/0 – 250 MCM
(3) #6 – 3/0 AWG
400
Standard
1
(2) #6 – 250 MCM
(2) #6 – 250 MCM
(1) #4 – 600 MCM
(2) 1/0 – 250 MCM
(3) #14 – 1/0 AWG
Service
Entrance
1
Normal: (2) 3/0 – 250
MCM
Emerg: (2) #6 -- 250
MCM
(2) #6 – 250 MCM
(3) #4 – 600 MCM
(6) 1/0 – 250 MCM
3-pole
208-240 V
3
(2) #6 – 250 MCM
(2) #6 – 250 MCM
(1) #4 – 600 MCM
(2) 1/0 – 250 MCM
3 or 4 pole
480 V
3
(1) #4 – 600 MCM
(2) #6 – 250 MCM
(1) #4 – 600 MCM
(2) #6 – 250 MCM
(1) #4 – 600 MCM
(2) 1/0 – 250 MCM
Figure 2-8
Cable Sizes
Summary of Contents for RXT
Page 10: ...TP 6807 12 11 10 Service Assistance Notes...
Page 24: ...TP 6807 12 11 24 Section 4 Service Disconnect SE Model Notes...
Page 28: ...TP 6807 12 11 28 Section 5 Scheduled Maintenance Notes...
Page 54: ...TP 6807 12 11 54 Section 5 Diagrams and Drawings Notes...
Page 57: ...TP 6807 12 11 57 Notes...
Page 58: ...TP 6807 12 11 58 Notes...
Page 59: ......