background image

TT-585 3/95a

INSTALLATION INSTRUCTIONS

Original Issue Date:

3/91

Model:

20-300 kW

Market:

Industrial

Subject:

Generator Strip Heater Kits PA-253213, PA-253213-SD

The generator strip heater kit heats the unit in cold
climates and helps prevent condensation from forming
in the generator.

Observe the following safety

precautions while installing the kit.

Accidental starting.
Can cause severe injury or death.

Disconnect the battery cables before
working

on

the

generator

set.

Remove the negative (--) lead first
when

disconnecting

the

battery.

Reconnect the negative (--) lead last
when reconnecting the battery.

WARNING

Disabling the generator set.

Accidental starting can

cause severe injury or death.

Before working on the

generator set or connected equipment, disable the generator
set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnect the power to the battery charger.
(3) Remove the battery cables, negative (--) lead first.
Reconnect the negative (--) lead last when reconnecting the
battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
start/stop switch, or engine start command from a remote
computer.

Hazardous voltage.
Can cause severe injury or death.

Operate the generator set only when
all guards and electrical enclosures
are in place.

Moving rotor.

WARNING

Grounding electrical equipment. Hazardous voltage can
cause severe injury or death.

Electrocution is possible

whenever electricity is present.

Open the main circuit

breakers of all power sources before servicing the equipment.
Configure the installation to electrically ground the generator
set, transfer switch, and related equipment and electrical
circuits to comply with applicable codes and standards. Never
contact electrical leads or appliances when standing in water
or on wet ground because these conditions increase the risk of
electrocution.

Disconnecting the electrical load. Hazardous voltage can
cause severe injury or death.

Disconnect the generator set

from the load by opening the line circuit breaker or by
disconnecting the generator set output leads from the transfer
switch and heavily taping the ends of the leads. High voltage
transferred to the load during testing may cause personal
injury and equipment damage. Do not use the safeguard
circuit breaker in place of the line circuit breaker.

The

safeguard circuit breaker does not disconnect the generator
set from the load.

Installation

1. Disconnect engine starting battery, negative (--)

lead first.

2. Disconnect generator set from load by opening line

circuit breaker or disconnecting output leads from
transfer switch and heavily taping end of leads.

3. Remove junction box panels to expose end bracket

and stator.

4. Connect AC leads to strip heaters. Position lead

terminals perpendicular to strip heater. See
Figure 1.

5. Assemble

strip

heaters

(291269),

screws

(X-465-8), washers (X-25-40), and spiral lock nuts
(X-6210-2) as shown in Figure 1. Install spiral lock
nuts so the flange is against the stator shell when
assembly is installed. Strip heater terminals must
be on the same side as the screw heads.
Assemble components hand-tight to allow strip
heater expansion and contraction.