Determine the System Layout (cont.)
Determine the location of the
water supplies
and
steam lines
. Ensure clearance between the steam
line and any surrounding surfaces.
Install this steam generator in a heated space to prevent freezing.
Ensure that this steam generator is installed level.
Allow for access to the steam generator after installation.
Select the steam generator size based upon the steam room volumes identified below.
NOTE:
For every additional foot of ceiling height above 8’ (2.4 m), choose the next largest steam
generator.
Steam Generator
Steam Room Volume - Cubic Feet (Cubic Meters)
5 kW
84 (2.4)
7 kW
112 (3.2)
9 kW
240 (6.8)
11 kW
317 (9.0)
18 kW
550 (15.6)
22 kW
634 (18.0)