Troubleshooting (cont.)
Symptom
Probable Cause
Recommended Action
C.
Solenoid
Plugged
•
Turn off the water supply.
•
Purge the urinal valve.
•
Remove the urinal valve cover.
•
Remove the solenoid assembly.
•
Check the solenoid holes for
debris.
•
Inspect the O-ring seals under
the solenoid for cuts or debris.
•
Clean if required. If damaged,
order a new solenoid assembly.
•
Reassemble the unit.
D.
Battery Life
Expired
•
Remove the urinal valve cover.
•
Remove the sensor assembly.
•
Remove the back of
sensor.NOTE: The unit requires
a standard 6-Volt lithium
battery. This item is not
available from Kohler but can
be purchased at many stores
locally.
•
Replace the battery.
•
Reassemble the unit.
E.
Solenoid Not
Working
•
Order and install a new
solenoid assembly.
•
Reassemble the unit.
4.
Sporadic
Flow
A.
Wires
Pinched or
Damaged
•
Remove the urinal valve cover.
•
If wires are cut or damaged,
order new solenoid or sensor
assembly.
•
Verify that both wires are
tucked inside the cover before
reassembling.
B.
Low Battery
•
Replace the Battery.
1025497-5-B
24
Kohler Co.