10
TT-1379
5/16
Note:
Always identify and correct the cause of a fault
shutdown before resetting the controller. Consult
the operation manual for guidance and items to
check.
Digital Gauge Fault Codes
Fault codes are displayed on the gauge when a fault
condition is detected.
See Figure 19 for faults displayed on the gauge for units
equipped with an ADC 2100 controller.
See Figure 20 for faults displayed on the gauge for units
equipped with an ADC II or ADC IId controller.
See Figure 21 for faults displayed on the gauge for units
equipped with a Decision-Maker
r
3500 controller.
Units with ADC 2100 Controller
Digital Gauge
Display
Description
LOP
Low Oil Pressure
OC
Over Crank
OS
Over Speed
LCL
Low Coolant Level
LOC
Loss of Coolant
AF
Auxiliary Input Fault
HE
High Engine Temperature
OU
Over Voltage
UU
Under Voltage
OF
Over Frequency
UF
Under Frequency
LB
Low Battery Voltage
HB
High Battery Voltage
Figure 19
Fault Codes Displayed on the Gauge (for
Units Equipped with an ADC 2100
Controller)
Units with ADC II or ADC IId Controller
Digital Gauge
Display
Description
LOP
Low Oil Pressure
OC
Over Crank
OS
Over Speed
AF
Auxiliary Input Fault
HE
High Engine Temperature
OU
Over Voltage
UU
Under Voltage
OF
Over Frequency
UF
Under Frequency
LB
Low Battery Voltage
HB
High Battery Voltage
Figure 20
Fault Codes Displayed on the Gauge (for
Units Equipped with an ADC II or ADC IId
Controller)
Units with Decision-Maker
r
3500 Controller
Digital Gauge
Display
Description
LOP
Low Oil Pressure
OS
Over Speed
AF
Auxiliary Input Fault
HE
High Engine Temperature
OU
Over Voltage
UU
Under Voltage
OF
Over Frequency
UF
Under Frequency
For other possible fault codes, the gauge displays:
SHdn
(for a Shutdown) or
Alrt
(for an Alert/Warning).
Check the interface on the Decision-Maker
r
3500 Controller for more
details.
Figure 21
Fault Codes Displayed on the Gauge (for
Units Equipped with an Decision-Maker
r
3500 Controller)