Section 2 Operation

Code

Fault

Description

Check

AF

Auxiliary fault
input shutdown

Input from a customer-supplied switch that closes
when the fault is active. The generator set shuts
down 0.3 seconds after the fault is detected and will
not start when the fault is active (input is grounded).
This protection becomes active 3 seconds after
crank disconnect.

Check the cause of the auxiliary fault.

HE

High engine
temperature
shutdown

Shutdown occurs if the engine coolant temperature
exceeds the maximum temperature for more than
5 seconds. This protective becomes active after the
engine reaches the crank disconnect speed.

Check for blocked air inlets and exhaust
outlets.

LCL

Low coolant
level

Not used.

LOC

Loss of coolant

Not used.

LOP

Low oil
pressure
shutdown

Shutdown occurs if a low oil pressure condition
exists for more than 5 seconds. This protective
becomes active 30 seconds after the engine has
reached crank disconnect speed (30 second inhibit).

Check for leaks in the lubrication system.

Check the oil level and add oil if the level is
low.

OC

Overcrank
shutdown

Shutdown occurs after 3 unsuccessful starting
attempts. The crank cycle is set for three starting
attempts of 15 seconds cranking and 15 seconds
rest.
The generator set also shuts down if no engine
rotation is sensed during cranking. Shuts down
1 second after the fault is detected.

Check the fuel supply, spark plug, and
battery.

Check for loose connections.

Contact an authorized Kohler distributor/
dealer for service if problem continues.

OF

Overfrequency
shutdown

Shutdown occurs when the governed frequency
exceeds 110% of the system’s frequency setpoint
for more than 5 seconds. This protective becomes
active 10 seconds after engine start (10 second
inhibit).

Contact an authorized Kohler
distributor/dealer for service if problem
continues.

OS

Overspeed
shutdown

Shutdown occurs if the engine speed exceeds 115%
of the normal running speed for more than
0.3 seconds.

Contact an authorized Kohler
distributor/dealer for service if problem
continues.

OU

Overvoltage
shutdown

Shutdown occurs if the voltage exceeds 120% of the
system nominal voltage for more than 2 seconds.

Contact an authorized Kohler distributor/
dealer for service if problem continues.

UF

Underfrequency
shutdown

Shutdown occurs when the governed frequency falls
below 90% of the nominal system frequency for
more than 5 seconds or below 59 Hz for more than
60 seconds. This protective becomes active
10 seconds after engine start. (10 second inhibit).

Reduce the load and restart the generator
set.

Contact an authorized Kohler
distributor/dealer for service if problem
continues.

UU

Undervoltage
shutdown

Shutdown occurs if the voltage falls below 80% of
the nominal system voltage for more than
10 seconds.

Reduce the load and restart the generator
set.

Contact an authorized Kohler distributor/
dealer for service if problem continues.

SCF0

Software
Communication
Fault 0

Indicates a software or communication problem
within the

ADC 2100

.

Replace the controller.

Figure 2-4

ADC 2100 Fault Shutdown Codes

Summary of Contents for 15RES

Page 1: ...Residential Generator Sets Models 15RES 30RES Controller Advanced Digital Control ADC 2100 TP 6344 4 09c Operation...

Page 2: ...s are readily available for future reference Record field installed kit numbers after installing the kits Generator Set Identification Numbers Record the product identification numbers from the genera...

Page 3: ...2 Service Schedule 20 3 3 Maintenance and Service Parts 21 3 4 Lubrication System 21 3 4 1 Oil Specifications 21 3 4 2 Oil Check 21 3 4 3 Optional Oil Makeup Low Level Shutdown Kit 21 3 4 4 Oil Addit...

Page 4: ...TP 6344 4 09 4 Notes...

Page 5: ...reconnecting the battery Follow these precautions to prevent starting of the generator set by an automatic transfer switch remote start stop switch or engine start command from a remote computer Batt...

Page 6: ...whenworking on or near the generator set Never operate the generator set inside a building unless the exhaust gas is piped safely outside Never operate the generator set where exhaust gas couldaccumul...

Page 7: ...generator set without first disconnecting the battery controller wiringharness andengineelectronic control module ECM CAUTION Grounding electrical equipment Hazardous voltage can cause severe injury o...

Page 8: ...or death Keep hands feet hair clothing and test leads away from the belts and pulleys when the generator set is running Replaceguards screens and covers before operating the generator set Heavy Equip...

Page 9: ...follow all procedures and safety precautions to ensure proper equipment operation and to avoid bodily injury Read and follow the Safety Precautions and Instructions section at the beginning of this ma...

Page 10: ...ice Headquarters Europe Middle East Africa EMEA Kohler Power Systems 3 rue de Brennus 93200 Saint Denis France Phone 33 1 49 178300 Fax 33 1 49 178301 Asia Pacific Power Systems Asia Pacific Regional...

Page 11: ...r 12 Positive battery connection point 13 Oil drain valve 14 Fuel solenoid valves two required for UL 2200 15 Fuel inlet 16 AC circuit breaker panel 17 Fuses 18 Generator set master switch 19 Advanced...

Page 12: ...TP 6344 4 09 12 Section 1 Service Views Notes...

Page 13: ...ponents become hot when the generator set is running and remain hot for a time after the generator set shuts down 2 2 Prestart Checklist To ensure continued satisfactory operation perform the followin...

Page 14: ...ection 2 4 6 The buttons on the controller keypad are used only for system configuration and adjustment The ADC 2100 is factory set and should not require configuration or adjustment under normal oper...

Page 15: ...e fault condition is corrected Shutdowns The generator set shuts down automatically under the conditions listed in Figure 2 4 and the controller displays a fault code Correct the fault condition and t...

Page 16: ...loose connections Contact an authorized Kohler distributor dealer for service if problem continues OF Overfrequency shutdown Shutdown occurs when the governed frequency exceeds 110 of the system s fre...

Page 17: ...he AUTO position the controller may power down after a period of inactivity The controller s communication parameter Cn setting determines the power down mode See the installation manual TP 6341 for c...

Page 18: ...TP 6344 4 09 18 Section 2 Operation Notes...

Page 19: ...only when all guards and electrical enclosures are in place Moving parts WARNING Servicing the generator set when it is operating Exposed moving parts can cause severe injury or death Keep hands feet...

Page 20: ...7 X Check the exhaust gas condition during operation 3 7 X Cooling System Check the coolant level and fill as necessary 3 8 1 X Inspect the radiator and hoses 3 8 1 X Check the belt tension and condi...

Page 21: ...or above the Full mark on the dipstick 1 TP 5586 3 2 1 Full mark 2 Add mark Figure 3 2 Oil Level Check 3 4 3 Optional Oil Makeup Low Level Shutdown Kit On generator sets equipped with the optional oi...

Page 22: ...the housing side panel 5 Stop the generator set Check the oil level Add oil as necessary to bring the level up to the Full mark Note Too high an oil level causes high oil consumption and engine carbo...

Page 23: ...and reattach the spring clips 3 7 Exhaust System Carbon monoxide Can cause severe nausea fainting or death The exhaust system must be leakproof and routinely inspected WARNING Carbon monoxide detecto...

Page 24: ...ated cap The pressure cap raises the boiling point of the coolant enabling higher operating temperatures If the cap leaks replace it with the same rating type of cap Find the pressure cap rating in Fi...

Page 25: ...acid Battery acid can cause severe injury or death Battery acid can cause blindness and burn skin Always wear splashproof safety goggles rubber gloves and boots when servicing the battery Do not open...

Page 26: ...ht tan or gray deposit on firing tip See Figure 3 9 to evaluate engine condition by color condition of a problem spark plug Problem Condition Means of Identification Possible Cause Solution Gap bridge...

Page 27: ...the center electrode to set the correct gap See Figure 3 11 Position the side electrode directly over the center electrode 1 511 Figure 3 11 Spark Plug Gap Adjustment 11 Reinstall the spark plug Do no...

Page 28: ...dure Follow the procedure below when storing your generator set for a long period 3 months or more 1 Start and run the generator set until it reaches operating temperature or about 15 minutes 2 Stop t...

Page 29: ...r and the load The line circuit breaker location is shown in Figure 1 1 If the circuit breaker trips reduce the load and switch the breaker back to the ON position 4 3 2 Fuses Three 10 amp fuses are l...

Page 30: ...output AC circuit breaker in the OFF position Place the circuit breaker in the ON position AC circuit breaker tripping because of overload Reduce the load on the generator set AC circuit breaker tripp...

Page 31: ...Controller display will automatically activate when a remote start command is received or the generator set master switch is moved to the RUN position Controller fuse F3 is blown Replace the fuse See...

Page 32: ...TP 6344 4 09 32 Section 4 Troubleshooting Notes...

Page 33: ...ter s Laboratories CUL Canadian Underwriter s Laboratories cu in cubic inch cw clockwise CWC city water cooled cyl cylinder D A digital to analog DAC digital to analog converter dB decibel dB A decibe...

Page 34: ...ersize overspeed OSHA Occupational Safety and Health Administration OV overvoltage oz ounce p pp page pages PC personal computer PCB printed circuit board pF picofarad PF power factor ph phase PHC Phi...

Page 35: ......

Page 36: ...CO Kohler Wisconsin 53044 Phone 920 565 3381 Fax 920 459 1646 For the nearest sales service outlet in the US and Canada phone 1 800 544 2444 KohlerPower com Kohler Power Systems Asia Pacific Headquart...

Reviews: