Section 5 Accessories

5.7.4

Oil Pressure Sensor Boot

The oil pressure sensor boot protects the oil pressure
sensor and its connection from moisture and frost
buildup that can cause false low oil level faults. Install
the oil pressure sensor boot in locations where the
ambient temperature drops below 0 C (32 F). See
Figure 5-20 for illustrations of the installed kit. Follow
the instructions provided with the kit to install the boot.

14 kW Models

1

1

20 kW Models

GM102176

1. Oil pressure sensor boot

Figure 5-20

Oil Pressure Sensor Boot Location

Summary of Contents for 14RCA

Page 1: ...Residential Commercial Generator Sets Models 14RCA 14RCAL 20RCA 20RCAL Controller RDC2 TP 7091 2 21a Installation...

Page 2: ...e generator Product Identification Information Generator Set Identification Numbers Record the product identification numbers from the generator set nameplate s Model Designation Specification Number...

Page 3: ...21 Section 3 Electrical 23 3 1 Electrical Connections 23 3 1 1 Wire Selection 23 3 1 2 Grounding 24 3 1 3 Electrical Lead Entry 24 3 1 4 Field Connections 25 3 1 5 AC Power Supply 26 3 2 Battery 27 3...

Page 4: ...Table of Contents continued TP 7091 2 21 Table of Contents 5 7 4 Oil Pressure Sensor Boot 46 Section 6 Drawings and Diagrams 47 Appendix A Abbreviations 61...

Page 5: ...o the set disable the generator set as follows 1 Press the generator set off reset button to shut down the generator set 2 Disconnect the power to the battery charger if equipped 3 Remove the battery...

Page 6: ...fuel vapors are flammable and explosive Handle these materials carefully to minimize the risk of fire or explosion Equip the compartment or nearby area with a fully charged fire extinguisher Select a...

Page 7: ...as Adequate ventilation is mandatory Because natural gas rises install natural gas detectors high in a room Inspect the detectors per the manufacturer s instructions Hazardous Noise Hazardous noise Ca...

Page 8: ...zardous backfeed voltage can cause severe injury or death Install a transfer switch in standby power installations to prevent the connection of standby and other sources of power Electrical backfeed i...

Page 9: ...injury Read and follow the Safety Precautions and Instructions section at the beginning of this manual aac11780 Figure 1 Generator Set List of Related Literature Figure 2 identifies related literature...

Page 10: ...s Europe Middle East Africa EMEA Kohler EMEA Headquarters Netherlands B V Kristallaan 1 4761 ZC Zevenbergen The Netherlands Phone 31 168 331630 Fax 31 168 331631 Asia Pacific Kohler Asia Pacific Headq...

Page 11: ...e installation complies with applicable national and local codes In the United States the installation must comply with the National Electrical Code NEC and local codes For Canadian installations refe...

Page 12: ...0 440 20RCA 252 555 Weights include generator set and packaging with skid no battery or ATS Figure 1 1 Approximate Weights 1 3 Generator Set Inspection Complete a thorough inspection of the generator...

Page 13: ...for the generator set Allow easy access for maintenance and service Support the weight of the generator set with related equipment such as the battery and mounting pad Support the generator set weight...

Page 14: ...r intake panel hangs on four 20 mm 0 8 in diameter bushings Pull the air intake panel up and off See Figure 1 5 3 To make the electrical connections you will also need to remove the cover panel over t...

Page 15: ...ratings and other fuel supply information for natural gas and LPG fuels Verify that the output pressure from the primary gas utility pressure regulator is within the range shown in Figure 2 1 and that...

Page 16: ...with the generator set fuel inlet and end about 12 inches away to allow connection with a section of flexible fuel line Use flexible sections to prevent fuel line breakage caused by vibration Note Do...

Page 17: ...om an authorized distributor dealer if necessary Provide the following information from the original nameplate Model Number kVA Spec Number Amps Serial Number Volts Fuel original and new Hz kW Attach...

Page 18: ...ver is required to remove and replace the fittings NG LPG Figure 2 5 NG and LPG Fuel Orifice Fittings The unit is typically shipped set up for natural gas with the LPG fitting tied near the fuel solen...

Page 19: ...ignition timing leads 65 and N3 for LPG The ignition timing leads are located near the top of the compartment See Figure 2 6 10 Connect and turn on the new fuel supply 11 Reconnect the generator set e...

Page 20: ...rator set engine starting battery negative lead first 4 Turn off the fuel supply 5 Remove the hose clamp and fuel hose from the hose fitting See Figure 2 8 6 Insert the LPG orifice into the hose fitti...

Page 21: ...n Revised Fuel System 1 Press the OFF button on the generator set controller 2 Disconnect utility power to the generator set open the corresponding circuit breaker in the distribution panel 3 Disconne...

Page 22: ...See the Operation Manual for instructions to change settings on the controller 11 Start the generator set by pressing the RUN button on the generator set controller 12 Check for leaks using a gas lea...

Page 23: ...n The circuit breaker must be rated for a maximum of 125 of the rated generator set output current The circuit breaker must open all ungrounded connectors The generator set is equipped with a factory...

Page 24: ...Code NEC local codes and the type of transfer switch used in the application determine the grounding of the neutral at the generator NEC Section 250 is one example that has a very good explanation of...

Page 25: ...onding connection points near the circuit breaker See Figure 3 3 Also see Section 3 1 2 Grounding 4 Connect AC power source leads to the terminal block connections labeled HOT NEUTRAL and GROUND Conne...

Page 26: ...onnector P6 on the back of the RDC2 controller 8 When connections are complete replace the cover plate 3 1 5 AC Power Supply The installer must connect AC power for the battery charger which is integr...

Page 27: ...ery gases Explosion can cause severe injury or death Battery gases can cause an explosion Do not smoke or permit flames or sparks to occur near a battery at any time particularly when it is charging D...

Page 28: ...on to the battery Use the following procedure to install and connect the battery Battery Installation Procedure 1 Ensure that the starting battery is fully charged before placing the battery in servic...

Page 29: ...s 3 3 2 Transfer Switch Connection Connect the ATS or remote start stop switch Connect the load leads from the generator set to the Emergency source lugs on the ATS Route low voltage communication lea...

Page 30: ...3 Note Generator set terminal block connections 3 and 4 are NOT USED with the Model RXT ATS RXT transfer switch with standard or combined interface load management board Generator Set GND RBUS 12 VDC...

Page 31: ...es and do not add to the number of modules in Figure 3 6 Generator Set GND A B COM PWR RBUS 12VDC RXT COM COM PWR COM PWR PWR B A B A B A COM PWR B A COM PWR B A 4 5 2 1 3 5 Load Shed Kit PIM COM PWR...

Page 32: ...ee Figure 3 6 for cable specifications including maximum total cable length 4 12 AWG or 14 AWG leads for PWR and COM 5 Connect shields together as shown 6 Leave one end of the cable shield disconnecte...

Page 33: ...ple leads for connection to the generator set terminal block See Figure 3 12 Terminal Block Load Shed Kit Figure 3 11 Accessory Module Connections three cable runs with one module each 2 tp6803 1 Gene...

Page 34: ...s See Section 3 3 1 Cable Specifications See Figure 3 9 for communication connection detail A and B PWR and COM Connect the cable shield to ground at the generator set Use splices or wire nuts to coll...

Page 35: ...on Stomachache vomiting nausea If experiencing any of these symptoms and carbon monoxide poisoning is possible seek fresh air immediately and remain active Do not sit lie down or fall asleep Alert oth...

Page 36: ...and the controller display shows the main menu See the generator set Operation Manual for more detailed instructions to set the date and time and set the exerciser Press AUTO to place the generator se...

Page 37: ...emperature drops below 0 C 32 F The carburetor heater prevents condensation and carburetor icing The heater turns on when the temperature at the thermostat falls below approximately 4 C 40 F and turns...

Page 38: ...show heater 2 Carburetor heater power cord 1 2 Figure 5 3 Carburetor Heater for 14 kW Models 2 tt1482b 1 adv 8954 1 Carburetor heater location under air cleaner Insert from the back of the generator s...

Page 39: ...gure 5 7 To change the input and output settings use a personal computer running Kohler SiteTech software See TP 6701 SiteTech Software Operation Manual for instructions SiteTech is available to Kohle...

Page 40: ...ose kit Use category 5E network cable to connect the RDC2 controller to the customer supplied Ethernet router or modem Route the cable with other low voltage signal wiring for example the RBUS communi...

Page 41: ...s can be powered by the generator set when the more important appliances are not running allowing the use of a smaller generator set than would be needed to run all of the building s electrical equipm...

Page 42: ...11 The APM provides a common connection point for paralleling generators and permits individual control of the generator connections allowing for synchronization redundancy and generator management Ge...

Page 43: ...gure 5 11 PowerSync Automatic Paralleling Module 5 7 Cold Weather Package The cold weather package is recommended for reliable operation at temperatures below 0 C 32 F The cold weather package include...

Page 44: ...r Verify that AC power is connected to the generator set as described in the generator set Installation Manual The circuit must be backed up by the generator set to provide power at all times Refer to...

Page 45: ...eaters The breather tube heating element wraps around the breather tube from the engine to the air cleaner Before installing the oil heater kit drain the oil from the engine Insert the oil heater near...

Page 46: ...up that can cause false low oil level faults Install the oil pressure sensor boot in locations where the ambient temperature drops below 0 C 32 F See Figure 5 20 for illustrations of the installed kit...

Page 47: ...clearance requirements single unit Sheet 4 51 Location and clearance requirements parallel units Sheet 5 52 Wiring Diagrams 14 20RCA RCAL Schematic Diagram ADV 9236 A Harnesses and cables Sheet 1 53...

Page 48: ...TP 7091 2 21 48 Section 3 Diagrams and Drawings Figure 6 2 Dimension Drawing ADV 9746 Sheet 1...

Page 49: ...TP 7091 2 21 49 Section 3 Diagrams and Drawings Figure 6 3 Dimension Drawing ADV 9746 Sheet 2...

Page 50: ...TP 7091 2 21 50 Section 3 Diagrams and Drawings Figure 6 4 Dimension Drawing ADV 9746 Sheet 3...

Page 51: ...TP 7091 2 21 51 Section 3 Diagrams and Drawings Figure 6 5 Dimension Drawing ADV 9746 Sheet 4...

Page 52: ...TP 7091 2 21 52 Section 3 Diagrams and Drawings Figure 6 6 Dimension Drawing ADV 9746 Sheet 5...

Page 53: ...TP 7091 2 21 53 Section 3 Diagrams and Drawings Figure 6 7 Schematic Diagram ADV 9236 Sheet 1...

Page 54: ...TP 7091 2 21 54 Section 3 Diagrams and Drawings Figure 6 8 Schematic Diagram ADV 9236 Sheet 2...

Page 55: ...TP 7091 2 21 55 Section 3 Diagrams and Drawings Figure 6 9 Schematic Diagram ADV 9236 Sheet 3...

Page 56: ...TP 7091 2 21 56 Section 3 Diagrams and Drawings Figure 6 10 Schematic Diagram ADV 9236 Sheet 4...

Page 57: ...TP 7091 2 21 57 Section 3 Diagrams and Drawings Figure 6 11 Wiring Diagram GM115458 Sheet 1 Single Phase 2 Pole Circuit Breaker...

Page 58: ...TP 7091 2 21 58 Section 3 Diagrams and Drawings Figure 6 12 Wiring Diagram GM115458 Sheet 2 Single Phase 1 Pole Circuit Breaker...

Page 59: ...TP 7091 2 21 59 Section 3 Diagrams and Drawings Figure 6 13 Wiring Diagram GM115458 Sheet 3 Three Phase 3 Pole Circuit Breaker...

Page 60: ...TP 7091 2 21 60 Section 3 Diagrams and Drawings Notes...

Page 61: ...ter s Laboratories cu in cubic inch cw clockwise CWC city water cooled cyl cylinder D A digital to analog DAC digital to analog converter dB decibel dB A decibel A weighted DC direct current DCR direc...

Page 62: ...tite screw PHH Phillips hex head screw PHM pan head machine screw PLC programmable logic control PMG permanent magnet generator pot potentiometer potential ppm parts per million PROM programmable read...

Page 63: ......

Page 64: ...ohler Co All rights reserved TP 7091 2 21a KOHLER CO Kohler Wisconsin 53044 Phone 920 457 4441 Fax 920 459 1646 For the nearest sales service outlet in the US and Canada phone 1 800 544 2444 KOHLERPow...

Reviews: