TP-6514 9/09
36
Section 1 Installation
Follow the instructions in Figure 1-42 to enter the
configuration mode while the engine is not running and
then step through the following parameters. Use the up
(
∧
) and down (
∨
) arrow buttons to select the appropriate
setting for the application.
The controller will automatically exit the configuration
mode without saving any changes after about 1 minute
if no buttons are pressed.
Start the configuration
procedure over again from the beginning if the controller
exits the configuration mode before the settings have
been saved.
Note:
Be sure to save your settings before exiting the
configuration mode. The controller reverts to the
last saved settings when the master switch is
moved to the OFF/RESET position.
Voltage/frequency setting (Uu).
Select the system
voltage and frequency from the table in Figure 1-41.
Note:
The Uu parameter sets the system’s rated
voltage and frequency.
To adjust the output
(measured) voltage and frequency, see Section
1.14, Voltage and Frequency Adjustments.
Engine configuration (Ec).
The engine configuration
must match the generator set engine type.
Communication/Sleep Mode Setting (Cn).
(Available
on controllers with application code version 1.13 or
higher.) The communication setting enables or disables
J1939 communication, and also disables or enables the
sleep mode. When J1939 communication is enabled,
the sleep mode is turned off to allow uninterrupted
communication with a personal computer running
remote monitoring software. If remote monitoring is not
used, the communication can be turned off, enabling the
sleep mode which causes the controller to power down
after 48 hours of inactivity. The generator set master
switch must be in AUTO for the sleep mode to function.
The default setting for controllers with application code
version 1.13 or higher is Cn01, communication on/sleep
mode off.
Controllers with earlier application code
versions have communication disabled and the sleep
mode enabled. The Cn setting is not adjustable on
these earlier versions.
1.13.2 Application Code Version
To check the application code version number, HOLD
the select button while moving the generator set master
switch to RUN. (The engine will not start when the select
button is held.) Wait about 5 seconds for the application
code version number to appear on the display. See
Figure 1-42.
Summary of Contents for 12RES