Commissioning the NGR
1
5
2.3 Foam commissioning (with factory settings)
For use in applications with a significant buildup of foam.
Performing foam calibration
1. Mount the sensor according to the installation conditions (see Chapter 1.4 "Installation conditions"
and 1.7 "Mounting the coaxial tube")
2. Log into expert mode (see Chapter 5.1 "Expert mode")
3. Empty the tank completely
○
The probe rod must be completely free from medium and foam.
○
Buildup must be removed from the probe.
○
The end of the probe must not be fixed to the bottom of the tank.
4. Select the measuring mode
○
Access the
EXPRT-CONFIG-MeasMd
menu using the arrow and Set pushbuttons, and configure
to
HiAcc
.
5. Perform empty calibration
Access the
EXPRT-FOAM-CalEmp
menu using the arrow and Set pushbuttons.
○
!CalOk:
proceed to step 6.
○
!faild:
Ensure that the tank is empty and repeat step 5.
6. Fill with medium (without foam) until the probe is covered by at least 200 mm. The maximum level
must remain 200 mm from the process connection, however.
7. Adjust the sensitivity
Exit the
EXPRT
menu with the ESC pushbutton. The
NGR
must now display a valid measured
value.
If the measured value is invalid, adjust the
TrsHld
value in the
EXPRT-CONFIG
menu.
Access the
EXPRT-CONFIG-T
rsHld menu using the arrow and Set pushbuttons.
The following information applies:
○
50%
= high sensitivity
○
100% = standard
○
200%
= low sensitivity
○
Value range 20 to 500%
8. Run
EXPRT-Foam-CalMe
d
○
!CalOk: Everything in working order, proceed to step 9
○
!faild: Carry out step 5 again
9. Check the foam calibration in
EXPRT-Foam-FomSta
○
active: Foam commissioning was completed successfully.
○
inactive: Commissioning unsuccessful. Please repeat the process.