Operating Instructions 

for 

Plug-On Display 

 

Model: AUF-1... 

 AUF-3... 

 AUF-4... 

 
 

Summary of Contents for AUF-1 series

Page 1: ...Operating Instructions for Plug On Display Model AUF 1 AUF 3 AUF 4...

Page 2: ...Mechanical Connection 4 7 Electrical Connection 5 8 Commissioning 7 9 Technical Information 10 10 Order Codes 11 11 Dimensions 11 12 Declaration of Conformance 12 Manufactured and sold by Kobold Messr...

Page 3: ...3 Instrument Inspection Instruments are inspected before shipping and sent out in perfect condition Should damage to a device be visible we recommend a thorough inspection of the delivery packaging In...

Page 4: ...decimal point gate time and switch point optional may be set with two keys The menu steps are output to the LED display field The Auf 4000 transforms the input pulses into a 4 20mA output signal 6 Me...

Page 5: ...Output 4 20 mA 2 wire 4 20 mA 2 wire switch out 4 20 mA 3 wire 4 20 mA 3 wire Auxiliary power only AUF 1 The auxiliary power typically 24 VDC must be greater than the voltage drop across the sensor t...

Page 6: ...nnection example AUF 1001 Connection example AUF 3000 AUF 4000 If the signal output is not used the signal output PIN 3 needs to be short circuited with GND PIN 2 Vs S 1 2 3 PE Switch Out GND S Ub Ua...

Page 7: ...isplayed Press A B to enter adjustment menu Press B or A for up and down Press A B to acknowledge setting and return to menu item dP 8 3 Zero Point value to be displayed for 4 mA Press key B until is...

Page 8: ...1 5 sec Press A B to acknowledge setting and return to menu item FILt 8 6 Range Exceeded indication of less than 4 mA or greater than 20 mA Indicates HI if the upper limit or LO if the lower limit is...

Page 9: ...001 optional Press key B until is displayed Press A B to enter adjustment menu hysteresis via switching point inverse Press B or A for up and down hysteresis below switching point Press A B to acknowl...

Page 10: ...load max 250 Max current load max 60 mA Conversion rate Three measurements s Gate time 0 3 20 s adjustable Data back up Non volatile EEPROM Error message HI overrange LO underflow Programming With two...

Page 11: ...4 20mA 2 wire AUF 1001 Plug on display with open collector 4 20mA 2 wire AUF 3000 Plug on display 4 20 mA 3 wire AUF 4000 Plug on display input pulses output 4 20 mA 3 wire Special Operating Instructi...

Page 12: ...with the standards noted below EN 61326 1 2013 Electrical equipment for measurement control and laboratory use EMC requirements Part 1 General requirements Also the following EU guidelines are fulfill...