EN
KPA FLEX-01
AC FLEXIBLE CLAMP
9 / 14
2
DESCRIPTION
1.
Flexible current coil
2.
Range switch
3.
Power switch
4.
Analog voltage output cable
5.
Power indication
6.
Turn knob
3
SPECIFICATIONS
Function
Range
Measurement
Range
Output Voltage
Accuracy
AC CURRENT
50~400Hz TRMS
30A AC
0,30A~30,00A
100mV/A
± (3,0% + 5mV)
300A AC
30,0A~300,0A
10mV/A
± (3,0% + 3mV)
3000A AC
300A~3000A
1mV/A
± (3,0% + 3mV)
Note: Accuracy is given as ± (% of r counts of least significant digit) at 23°C ± 5°C, with relative humid-
ity less 80%RH. The measured conductor is placed in the center of the coil.
Output Noise
<5,5mV for each range
Max output voltage
5,8V. All scale, if the output voltage is greater than 3V, the
results indicate that the measurement has been out of range,
not to be used as
Power indication:
Green LED light
Low Battery indication:
Red LED light
Operation Temperature:
41 ºF to 104 ºF (5ºC a 40ºC)
Storage temperature:
-4 ºF to 140 ºF (-20ºC a 60ºC)
Operation Humidity:
Max. 80% up to 87ºF (31ºC) decreasing linearly to 50% at 104
ºF (40ºC)
Storage Humidity:
<80%
Operating height:
7000 ft. (2000 meters) maximum.
Battery Safety:
1,5V “AAA” Size Battery x 2
Standard:
EN61010-1, EN61010-2-032, EN61326-1, Overvoltage Cate-
gory III 1000V and Category IV 600V, Pollution Degree 2.