Spec Sheet
Fire-extinguishing Systems
K-SLE & K-SLV Installation
KÖB & SCHÄFER GmbH, Flotzbachstr. 33, A-6922 Wolfurt, Tel. +43/5574/6770-0, Fax 65707, E-Mail: [email protected]
We reserve the right to make technical changes.
4550-1
2005-01-31_E
a)
Fire-extinguishing System for Burner Slide-in Module, Art. No. K-SLE
Note
: Pyromat-DYN has an extra charge with Art. No. K-SLE (see Spec Sheet 4500)
With Pyrot and Pyrtec this is included in the burner article.
Fig. 1: K-SLE on feed auger
b) Fire-extinguishing System for Material Feed Facility, Art. No. K-SLV
For Köb scope of delivery, refer to Spec Sheet 4500
Fig. 2: K-SLV on conveyor auger
Fig. 3: K-SLV on extractor system situated on top with
downpipe
Be sure to note:
•
The lines must be executed in metal (1/2") with fixed pipework (K-SLE and K-SLV).
•
It must not be possible to shut off the cold water inlet without the aid of tools.
•
Be especially sure to comply with Point 5 of the Installation Instructions (Fire Prevention).
Note:
K-SLV is an alternative or supplementary safety device. As standard, either a slide valve (Art. No. MBA-.; included in
Article ADF_.,. / ADE_3,0) is required for pressureless material storage sites or a rotary valve (Art. No. MBZ-.) for
material storage sites with over- or under-pressure (loading with fan, such as wood-processing businesses).
•
Line from container to the ½"
valve (short as possible)
•
Valve adjustment,
Danfoss AVTA 15 50-90°C
3, equivalent to approx. 80° C
KW: cold water inlet
DN 15 ½"
Min. 2.0, max. 3.0 bar
extinguisher water container 25 l
N25 level monitoring system
firing
material feed facility
CW
metering container
metering container
firing
with isolating layer
with isolating layer
CW
firing
Summary of Contents for KOB PYRTEC SERIES
Page 1: ...Assembly and Installation Instructions 530 to 1250 ID 104661 F english ...
Page 15: ......
Page 16: ......
Page 39: ......