Dimming actuator 1-gang 200 W with binary input, 3-gang

Mains frequency

50 / 60 Hz

Power loss

max. 1.5 W

Standby power

approx. 0.2 W

Ambient temperature

-5 ... +45 °C

Storage/transport temperature

-25 ... +70 °C

Dimensions (W × H × D)

48 x 50 x 28 mm

KNX
KNX medium

TP256

Commissioning mode

S-mode

Rated voltage KNX

DC 21 ... 32 V SELV

Current consumption KNX

5 ... 18 mA

Connection mode KNX

Connection terminal on control cable

Output
Connection mode

Screw terminals

Rated voltage

AC 230 / 240 V ~

Connected load depends on the connected lamps and set load type: (Figure 6) and (Figure 7)

ETS parameter load type

UNI

universal (with automatic calibration procedure)

LJ

conv. transformer (inductive / leading edge phase control)

|

LED (leading edge phase control)

dž

electr. transformer (capacitive / trailing edge phase control)

{

LED (trailing edge phase control)

Figure 6: Connected load LED lamps

7 / 10

82404402

02.02.2021

Summary of Contents for 506500

Page 1: ...f at least 4 mm must be maintained between bus conductors and mains voltage cores Danger of electric shock on the KNX installation Do not connect any external voltage to the in puts The device might be damaged and the SELV potential on the KNX bus line will no longer be available Fire hazard For operation with inductive transformers each transformer must be fused on the primary side in accordance ...

Page 2: ...offers protection against manipula tion in building automation and can be configured in the ETS project Detailed specialist know ledge is required A device certificate which is attached to the device is required for safe com missioning During mounting the certificate must be removed from the device and stored se curely Planning installation and commissioning of the device are carried out with the ...

Page 3: ...ery state Operation of the output via extension inputs 1 and 2 possible with existing supply via KNX Flickering of the connected lamps due to undershoot of the specified minimum load or through centralised pulses from the power stations This does not represent any defect in the device Characteristics extension inputs Switching operating function Dimming operating function incl colour temperature d...

Page 4: ...on wall or separate appliance boxes Connecting and fitting the device In secure operation preconditions Secure commissioning is activated in the ETS Device certificate entered scanned or added to the ETS project A high resolution camera should be used to scan the QR code Document all passwords and keep them safe Mounting in suitable appliance box recommendation electronic device box with partition...

Page 5: ... removed from the device and stored securely The COM reference potential must not be connected together with COM connections of other devices 4 2 Commissioning Commissioning the device In the as delivered state the actuator is passive i e no telegrams are transmitted to the KNX The output is set to the universal dimming principle with automatic recognition of the load type Control of the output is...

Page 6: ...lashing slowly The safe state mode is activated With a new brief press of the programming button the programming mode can be switched on and off as usual also in the safe state mode If Programming mode is active the programming LED stops flashing Deactivating safe state mode Switch off bus voltage wait approx 10 s or carry out ETS programming Master reset The master reset restores the basic device...

Page 7: ...X 5 18 mA Connection mode KNX Connection terminal on control cable Output Connection mode Screw terminals Rated voltage AC 230 240 V Connected load depends on the connected lamps and set load type Figure 6 and Figure 7 ETS parameter load type UNI universal with automatic calibration procedure LJ conv transformer inductive leading edge phase control LED leading edge phase control dž electr transforme...

Page 8: ...ength of extension unit cable max 10 m Cable type preferably J Y St Y Poll voltage extension inputs approx 5 V 6 Troubleshooting Connected LED lamps or compact fluorescent lamps switch off in the lowest dimming position or flicker The set minimum brightness is too low Increase minimum brightness Connected LED lamps or compact fluorescent lamps flicker Cause 1 Lamps are not dimmable Check manufactu...

Page 9: ...ailing edge phase control Check the operation in the HV LED leading edge phase control setting reduce the connected load as well if necessary Exchange lamps for another type The response of the surge protection can be signalled by sending a short circuit telegram or can be determined by polling the short circuit communication object Cause 3 short circuit in output circuit Disconnect the output fro...

Page 10: ...another type of LED lamp or an LED lamp of another manufacturer 7 Accessories Remote sensor NTC temperature sensor 1493 00 Condensation sensor 5069 00 Leakage sensor 5068 00 8 Warranty The warranty is provided in accordance with statutory requirements via the specialist trade Please submit or send faulty devices postage paid together with an error description to your re sponsible salesperson speci...

Reviews: