Dimming actuator, 4-gang

Switch on the mains voltage of the outputs again. Switch the affected output off and on
again.

When a short-circuit occurs the affected output switches off. Automatic restart when short-
circuit is eliminated within 100 ms (inductive load) or 7 seconds (capacitive or ohmic
load). After that lasting switch-off.

When a short-circuit occurs during the calibration process, the load calibrates itself again
after the short-circuit is eliminated.

Cause 4: load failure.

Check load, replace light bulb. For inductive transformers, check primary fuse and replace
if necessary.

Manual control with button field not possible

Cause 1: Manual control has not been programmed.

Program manual control.

Cause 2: Manual control via bus disabled.

Enable manual control.

None of the outputs can be operated.

Cause 1: All of the outputs are disabled-

Cancel disabling.

Cause 2: Manual mode active.

Deactivate manual mode (switch off continuous manual mode).

Cause 3: Application software missing or faulty.

Check programming and correct.

All outputs off and not possible to switch on

Cause 1: bus voltage failure.

Check bus voltage.

Luminaires flicker or buzz, proper dimming not possible, device buzzes

Cause: wrong dimming principle set

Installation or commissioning error. Disconnect device and luminaire, switch off circuit
breaker.
Check installation and correct.
If the wrong dimming principle has been preselected: Set correct dimming principle.
If dimming actuator calibrates itself incorrectly, e.g. with highly inductive mains or long
load cables: preselect correct dimming principle with commissioning.

LED lamp is dimly lit when dimmer is switched off

Cause: LED lamp is not optimally suited for this dimmer.

Use a compensation module, see accessories.
Use another type of LED lamp or an LED lamp of another manufacturer.

8

Accessories

Compensation module LED

Order no. 2375 00

9

Warranty

The warranty is provided in accordance with statutory requirements via the specialist trade.
Please submit or send faulty devices postage paid together with an error description to your re-
sponsible salesperson (specialist trade/installation company/electrical specialist trade). They will
forward the devices to the Gira Service Center.

10 / 11

82402712

10.07.2020

Summary of Contents for 2015 00

Page 1: ...the set operating mode and load type do not match Set the correct dimming principle before connecting or exchanging the load Fire hazard For operation with inductive transformers each transformer must...

Page 2: ...s are connected observe the data of the transformer manufacturer on loads and the dimming principle HV LED and compact fluorescent lamps generate high pulsed currents when they are operated in the lea...

Page 3: ...ue switch 4 Operation Operating elements Figure 2 Operating elements 4 Status LEDs for outputs on output switched on 1 100 flashes at 1 Hz short circuit or manual mode flashes at 2 Hz overload mains v...

Page 4: ...manual control the outputs depending on the programming switch to the active position e g forced position logic operation Switching on permanent manual control Operation using the button field is prog...

Page 5: ...device and stored securely Connecting the device Connect bus line with KNX connecting terminal according to their correct polarity Attach the cover cap to the KNX connection as protection against haz...

Page 6: ...mode stops the execution of the loaded application program Only the system software of the device is still functional ETS diagnosis functions and pro gramming of the device are possible Manual operati...

Page 7: ...fter ap prox 5 s Restoring the device to factory settings Devices can be reset to factory settings with the Gira ETS Service App This function uses the firmware contained in the device that was active...

Page 8: ...load is not permitted Power boosters See power booster instructions Connection single stranded 0 5 4 mm Finely stranded without conductor sleeve 0 5 4 mm Finely stranded with conductor sleeve 0 5 2 5...

Page 9: ...mming principle does not optimally match the connected lamps Check operation in the HV LED leading edge phase control setting reduce connected load as well if necessary Exchange lamps for another type...

Page 10: ...rect All outputs off and not possible to switch on Cause 1 bus voltage failure Check bus voltage Luminaires flicker or buzz proper dimming not possible device buzzes Cause wrong dimming principle set...

Page 11: ...GmbH Co KG Elektro Installations Systeme Industriegebiet Mermbach Dahlienstra e 42477 Radevormwald Postfach 12 20 42461 Radevormwald Deutschland Tel 49 0 21 95 602 0 Fax 49 0 21 95 602 191 www gira de...

Reviews: