3
Troubleshooting
Service Manual
34
Table 3-1 Troubleshooting Chart - No Display
FAULT
CAUSE
CORRECTIVE ACTION
No Display
- No 120 vac supplied to unit.
• Check external line switch, fuse, or breaker.
• Check 120 vac.
• Check wiring harness ribbon cable connection
between display board and main control board.
Connect
harness at both points.
- Bad display board.
• Replace board.
- Bad main control board.
• Replace the main control board.
- Blown fuse.
• Replace fuse F3 on the main control board, see
page 33 of this manual.
No Burner
Operation
- Main control board temperature set point
satisfied.
• Review temperature setting.
- Remote thermostat(s) satisfied.
• Review remote thermostat setting.
- Outside air temperature above Warm
Weather Shutdown (WWSD) set point for
main control board.
• Check location of outside air sensor. Check
resistance of outdoor air sensor and compare to Table
3-2B on page 35 of this manual.
- Unit locked out on fault.
• Consult display for specific fault. Refer to fault
descriptions on page 37 - 44
of this manual for
corrective actions.
- Unit in Shutdown Mode.
• Take unit out of Shutdown Mode.
Unit Does
Not Modulate
Above 50%
- Ramp delay active.
• Check ramp delay parameter settings.
• Turn ramp delay feature off. See page 23 of this
manual for instructions on how to turn this feature off.
- Boiler controlled by BMS.
• Check BMS parameter settings.
- No flue temperature change.
• Verify that the flue sensor is located in the flue outlet.
• Check wiring connections at the flue sensor.
• Check the resistance of the flue sensor and compare
to Table 3-2D on page 35 of this manual.